How Long Does a 500 kVA UPS Work? Duration Table and Calculation

How Long Does a 500 kVA UPS Work? Duration Table and Calculation

500 kVA level; It is installed for large data centers, hospital campuses, OSB facilities, airports and telecom centers. At this power, the total DC current at full load exceeds 1000 amps and the system almost always consists of parallel units. In this article, we explained the time table, calculation method and how much battery can be connected to the system.

Short answer

The battery pack of a 500 kVA UPS system is usually 480 V DC (40 12 V blocks or 240 2 V cells). Some manufacturers use different voltages, such as 576 V. A single battery string is not enough at this power. Multiple strings are connected in parallel and the time is total Ah value determined accordingly. In this article, all times are given over the total Ah. Approximate times:

  • At full load (approx. 450000 W) with a total of 2000 Ah: approx. 1 hour and 5 minutes
  • At full load with a total of 3000 Ah: approx. 1 hour and 50 minutes
  • At half load (approx. 225000 W) with a total of 3000 Ah: approx. 4 hours and 20 minutes
  • At full load with a total of 5000 Ah: approx. 3 hours 30 minutes

The calculations were made with 90% efficiency and 0.9 power factor. Since the efficiency of the new generation large UPSs is higher, the actual times may be a little longer. In most projects, the target time is 10-30 minutes. This time acts as a bridge until the generator is activated.

How many watts does a 500 kVA UPS carry?

  • In the system with a power factor of 0.9, 500 kVA is approximately 450000 W does.
  • In the new generation model with a power factor of 1,0 500000 W does.
  • In the old model with a power factor of 0.8 400000 W does.

The power factor is written in the data sheet. See What is Power Factor?.

Large battery hall with several 2 V cells arranged in long racks

Time table for 500 kVA UPS (480 V DC, total Ah)

Durations for new VRLA/AGM battery (2 V cell), 25 °C and 0.9 power factor and 90% UPS efficiency They are rough calculations. The actual time may deviate by 20-30% ± depending on the model. "Total Ah" is the sum of the Ah values of all 480 V arrays connected in parallel.

Total battery capacityFull load (450000 W)75% load (337500 W)Half load (225000 W)25% load (112500 W)
1500 Ah44 min1 hr 5 min1 hr 50 min4 hr 20 min
2000 Ah1 hr 5 min1 hr 34 min2 hr 40 min6 h
3000 Ah1 hr 50 min2 hr 40 min4 hr 20 min9 hr 30 min
4000 Ah2 hr 40 min3 hr 45 min6 hOver 12 h
5000 Ah3 hr 30 min4 hr 50 min7 hr 45 minOver 12 h

The calculation loses its reliability for periods above 12 hours. A generator solution is used for such a long time at this power.

UPS-protected campus data center corridor

Example calculation: 360000 W load on airport and data center campus

On a campus, the data center, terminal computing, security systems and critical lighting draw a total of 360000 W. The UPS system has a 480 V DC input, the total battery capacity is 3000 Ah.

  1. Battery energy: 480 V × 3000 Ah = 1440000 Wh.
  2. Current: 360000 ÷ (0.9 × 40 × 11.5 V) = approximately 870 A (sum of all sequences).
  3. C-rate: 870 ÷ 3000 = approximately 0.29.
  4. Available rate: Since the C-ratio is between 0.2-0.5, 0.60 (for the ratio table 1 kVA inscription see).
  5. Duration: 1440000 × 0.60 ÷ 360000 = 2.4 hours, so about 144 minutes.

If the target is 3 hours and 15 minutes, repeat with the group of 4000 Ah total: Wh = 1920000, C-ratio approx. 0.22, ratio 0.60. Duration = 1920000 × 0.60 ÷ 360000 = approx 192 minutes.

For load analysis, see. UPS and Battery Capacity Project Design.

Two engineers inspecting battery racks in battery hall

What is the maximum amount of battery connected to a 500 kVA UPS?

The number of batteries is fixed, the number of parallel strings is limited

Each string connects 240 2 V cells (480 V) in series. You cannot change this number. To extend the time, the cell Ah value is enlarged or a parallel array is added. At this power, the battery system usually consists of independent strings per unit. The highest number of parallel strings in the manufacturer's data sheet and the total Ah limit must be observed. See What is a Battery String?.

Charging current is the most important limit

At this power, the charging current is not provided by a single circuit. The charging circuit of each UPS unit is collected or a separate charging rectifier is added. The exact value is in the data sheet.

Rule: Ah = charging current × 10 (comfortable) to 20 × (limit).

Total charging currentRecommended maximum total battery (Ah)Full charge time (roughly)
100 A1000-2000 Ah12-24 hours
200 A2000-4000 Ah12-24 hours
400 A4000-8000 Ah12-24 hours
800 A8000-16000 Ah12-24 hours

Coarse charging time: Ah × 1.2 ÷ charging current (hours). In the example above, a total charging current of 150-300 A is required for 3000 Ah, and 200-400 A for 4000 Ah.

DC current, busbar and protection

The total DC current at full load is approximately 1087 A. This current does not flow through a single string. Each string must have its own DC fuse and switch. Copper busbar cross-sections, short-circuit strength, and busbar distances require project engineering.

Weight, space and ventilation

A group of 2 V cells of 480 V weighs roughly 15 kg × Ah. For example, 3000 Ah holds about 45 tons, 5000 Ah about 75 tons. For these weights, the floor load and rack carrying capacity must be verified by static calculation before installation. Ventilation, temperature and fire safety are planned separately in the battery room. See Factors Affecting Battery Life.

Lithium option

If space and weight are a problem, a lithium battery is also an option. See Lithium-Ion UPS Batteries and What is Thermal Runaway? How to Prevent It in Batteries?. For 2 V cells, see V. What is OPzS and OPzV Battery?.

Security: 480 V DC is life-threatening. Battery addition, connection and insurance are the work of authorized personnel.

Is 500 kVA a single UPS or a system?

Typical solutions for 500 kVA are two 250 kVA plus one redundant unit (N+1), five 100 kVA modular structures, or three 200 kVA parallel systems. To avoid a single point of failure at this scale, most projects are designed with a 2N or N+1 architecture. The parallel unit limit varies by manufacturer. See What is a Modular UPS?, What is Redundancy in UPS?, Parallel UPS Installation and Load Sharing and UPS Architecture in Data Centers.

Summary for all kVA classes on one page: How Long Does a UPS Work? kVA Guide

Frequently Asked Questions

01Will a 500 kVA UPS run for 1 hour?
At a load of up to 225000 W, you get about 4 hours and 20 minutes with a total group of 3000 Ah, and about 2 hours and 40 minutes with a group of 2000 Ah. For 1 hour at full load, a group of about 1900 Ah is required.
02Is a battery room required for a 500 kVA UPS?
Yes, as well as a large battery room. The rack requires ventilation, temperature control, fire safety, and floor bearing capacity.
03Do I need a generator?
If the goal is to run longer than 30 minutes at full load, the generator is almost always more economical. See Differences Between UPS and Generator.
04How do I verify duration?
The most reliable method is the discharge test. See Discharge and Load Tests.

Let's Choose the Right UPS Together