TCMB foreign exchange selling rate · 25.11.2026: USD 50,64 ₺ EUR 55,40 ₺

How Long Does an 800 kVA UPS Work? Duration Table and Calculation

How Long Does an 800 kVA UPS Work? Duration Table and Calculation

800 kVA level; It is a multi-unit system installed for large data centers, hospital campuses, refineries, airports and large industrial facilities. At full load, the total DC current exceeds 1700 amperes. At this scale, the battery system is a separate building section and a separate engineering project. In this article, we explained the time table, the calculation method and the maximum amount of battery that can be connected to the system.

Short answer

The battery bank of an 800 kVA UPS system is usually 480 V DC (40 12 V blocks or 240 2 V cells). Some manufacturers use different voltages, such as 576 V. A single battery string is not enough at this power. Multiple strings are connected in parallel and the time is total Ah value determined accordingly. In this article, all times are given over the total Ah. Approximate times:

  • At full load (approx. 720000 W) with a total of 3000 Ah: approx. 59 minutes
  • At full load with a total of 4000 Ah: approx. 1 hour 27 minutes
  • At half load (approx. 360000 W) with a total of 4000 Ah: approx. 3 hours 30 minutes
  • At full load with a total of 8000 Ah: approx. 3 hours 30 minutes

The calculations were made with 90% efficiency and 0.9 power factor. Since the efficiency of the new generation large UPSs is higher, the actual times may be a little longer. In most projects, the target time is 10-30 minutes. This time acts as a bridge until the generator is activated.

How many watts does an 800 kVA UPS carry?

  • In the system with a power factor of 0.9, 800 kVA is approximately 720000 W does.
  • In the new generation model with a power factor of 1,0 800000 W does.
  • In the old model with a power factor of 0.8 640000 W does.

The power factor is written in the data sheet. See What is Power Factor?.

Large multi-array battery room, each string connected to its own DC switch

Time table for 800 kVA UPS (480 V DC, total Ah)

Durations for new VRLA/AGM battery (2 V cell), 25 °C and 0.9 power factor and 90% UPS efficiency They are rough calculations. The actual time may deviate by 20-30% ± depending on the model. "Total Ah" is the sum of the Ah values of all 480 V arrays connected in parallel.

Total battery capacityFull load (720000 W)75% load (540000 W)Half load (360000 W)25% load (180000 W)
2000 Ah35 min51 min1 hr 27 min3 hr 30 min
3000 Ah59 min1 hr 27 min2 hr 25 min5 hr 35 min
4000 Ah1 hr 27 min2 hr 5 min3 hr 30 min7 hr 45 min
6000 Ah2 hr 25 min3 hr 30 min5 hr 35 minOver 12 h
8000 Ah3 hr 30 min4 hr 50 min7 hr 45 minOver 12 h

The calculation loses its reliability for periods above 12 hours. A generator solution is used for such a long time at this power.

Industrial plant process control room protected by UPS

Example calculation: 520000 W load in refinery and industrial plant

In a refinery and industrial facility, process control systems, security systems, data center and emergency lighting draw a total of 520000 W. The UPS system has a 480 V DC input, the total battery capacity is 4000 Ah.

  1. Battery energy: 480 V × 4000 Ah = 1920000 Wh.
  2. Current: 520000 ÷ (0.9 × 40 × 11.5 V) = approximately 1256 A (sum of all sequences).
  3. C-rate: 1256 ÷ 4000 = approximately 0.31.
  4. Available rate: Since the C-ratio is between 0.2-0.5, 0.60 (for the ratio table 1 kVA inscription see).
  5. Duration: 1920000 × 0.60 ÷ 520000 = 2.22 hours, so about 133 minutes.

If the target is 3 hours, repeat with the group of 6000 Ah total: Wh = 2880000, C-ratio approx. 0.21, ratio 0.60. Duration = 2880000 × 0.60 ÷ 520000 = approx 199 minutes.

For load analysis, see. UPS and Battery Capacity Project Design.

Ventilation ducts, smoke detector and fire extinguishing system in the battery room

What is the maximum amount of battery connected to an 800 kVA UPS?

The number of batteries is fixed, the number of parallel strings is limited

Each array connects 240 2 V cells (480 V) in series. You cannot change this number. To extend the time, the cell Ah value is enlarged or a parallel array is added. At this scale, the battery system consists mostly of independent strings per unit, with a total capacity of between a few hundred and several thousand Ah. The highest number of parallel strings in the manufacturer's data sheet and the total Ah limit must be observed. See What is a Battery String?.

Charging current is the most important limit

At this power, the charging current is not provided by a single circuit. The charging circuit of each UPS unit is collected or a separate charging rectifier is added. The exact value is in the data sheet.

Rule: Ah = charging current × 10 (comfortable) to 20 × (limit).

Total charging currentRecommended maximum total battery (Ah)Full charge time (roughly)
100 A1000-2000 Ah12-24 hours
200 A2000-4000 Ah12-24 hours
400 A4000-8000 Ah12-24 hours
800 A8000-16000 Ah12-24 hours

Rough charging time: Ah × 1.2 ÷ charging current (hours). In the example above, a total charging current of 200-400 A is required for 4000 Ah, and 300-600 A for 6000 Ah.

DC current, busbar and protection

The total DC current at full load is approximately 1739 A. This current does not flow through a single string. Each string must have its own DC fuse and switch. Copper busbar cross-sections, short-circuit strength, and busbar distances require project engineering.

Weight, space and ventilation

A group of 480 V cells with 2 V cells weighs roughly 15 kg × Ah. For example, 4000 Ah holds about 60 tons, 8000 Ah about 120 tons. For these weights, the floor load and rack bearing capacity must be verified by static calculation before installation. Ventilation, temperature and fire safety are planned separately in the battery room. See Factors Affecting Battery Life.

Lithium option

If space and weight are a problem, a lithium battery is also an option. See Lithium-Ion UPS Batteries and What is Thermal Runaway? How to Prevent It in Batteries?. For 2 V cells, see V. What is OPzS and OPzV Battery?.

Security: 480 V DC is life-threatening. Battery addition, connection and insurance are the work of authorized personnel.

Is 800 kVA a single UPS or a system?

800 kVA as a single unit is rare. Typical solutions are four 200 kVA, three 300 kVA or modular construction. In most projects, an N+1 or 2N architecture is installed. The battery system is planned independently of the UPS: the battery room, ventilation, fire extinguishing and maintenance access are designed together. See What is a Modular UPS?, What is Redundancy in UPS?, Parallel UPS Installation and Load Sharing and UPS Architecture in Data Centers.

Summary for all kVA classes on one page: How Long Does a UPS Work? kVA Guide

Frequently Asked Questions

01Does an 800 kVA UPS run for 1 hour?
With a total group of 4000 Ah, you get about 3 hours and 30 minutes with a group of 3000 Ah, and about 2 hours and 25 minutes with a group of 3000 Ah, with a load of up to 360000 W. For 1 hour at full load, a group of about 3000 Ah is required.
02Is a battery room required for an 800 kVA UPS?
Yes, as well as a large battery room. The rack requires ventilation, temperature control, fire safety, and floor bearing capacity.
03Do I need a generator?
If the goal is to run longer than 30 minutes at full load, the generator is almost always more economical. See Differences Between UPS and Generator.
04How do I verify duration?
The most reliable method is the discharge test. See Discharge and Load Tests.

Let's Choose the Right UPS Together

Bempower https://www.bemenerji.com/en/blog/how-long-does-an-800-kva-ups-work-duration-table-and-calculation
Write via WhatsApp