How Long Does a 300 kVA UPS Work? Duration Table and Calculation
300 kVA UPS; It is used for large data centers, hospitals, airports and heavy industry facilities. At this power, DC current reaches 650 amps at full load. The battery system is a battery room with multiple strings and a separate engineering project. In this article, we explained the time table, calculation method and how many batteries can be connected to the system.
Short answer
The battery bank of a 300 kVA UPS system is usually 480 V DC (40 12 V blocks or 240 2 V cells). Some manufacturers use different voltages, such as 576 V. A single battery string is not enough at this power. Multiple strings are connected in parallel and the time is total Ah value determined accordingly. In this article, all times are given over the total Ah. Approximate times:
- At full load (approx. 270000 W) with a total of 1000 Ah: approx. 51 minutes
- At full load with a total of 1500 Ah: approx. 1 hour and 27 minutes
- At half load (approx. 135000 W) with a total of 1500 Ah: approx. 3 hours 30 minutes
- At full load with a total of 3000 Ah: approx. 3 hours 30 minutes
The calculations were made with 90% efficiency and 0.9 power factor. Since the efficiency of the new generation large UPSs is higher, the actual times may be a little longer. In most projects, the target time is 10-30 minutes. This time acts as a bridge until the generator is activated.
How many watts does a 300 kVA UPS carry?
- In the system with a power factor of 0.9, 300 kVA is approximately 270000 W does.
- In the new generation model with a power factor of 1,0 300000 W does.
- In the old model with a power factor of 0.8 240000 W does.
The power factor is written in the data sheet. See What is Power Factor?.

Time table for 300 kVA UPS (480 V DC, total Ah)
Durations for new VRLA/AGM battery (2 V cell), 25 °C and 0.9 power factor and 90% UPS efficiency They are rough calculations. The actual time may deviate by 20-30% ± depending on the model. "Total Ah" is the sum of the Ah values of all 480 V arrays connected in parallel.
| Total battery capacity | Full load (270000 W) | 75% load (202500 W) | Half load (135000 W) | 25% load (67500 W) |
|---|---|---|---|---|
| 800 Ah | 38 min | 55 min | 1 hr 34 min | 3 hr 45 min |
| 1000 Ah | 51 min | 1 hr 14 min | 2 hr 5 min | 4 hr 50 min |
| 1500 Ah | 1 hr 27 min | 2 hr 5 min | 3 hr 30 min | 7 hr 45 min |
| 2000 Ah | 2 hr 5 min | 3 h | 4 hr 50 min | 10 hr 40 min |
| 3000 Ah | 3 hr 30 min | 4 hr 50 min | 7 hr 45 min | Over 12 h |
The calculation loses its reliability for periods above 12 hours. A generator solution is used for such a long time at this power.

Example calculation: 200000 W load at the airport
Terminal IT, baggage control system, security and emergency lighting at an airport draw a total of 200000 W. The UPS system has 480 V DC input, the total battery capacity is 1500 Ah.
- Battery energy: 480 V × 1500 Ah = 720000 Wh.
- Current: 200000 ÷ (0.9 × 40 × 11.5 V) = approximately 483 A (sum of all sequences).
- C-rate: 483 ÷ 1500 = approximately 0.32.
- Available rate: Since the C-ratio is between 0.2-0.5, 0.60 (for the ratio table 1 kVA inscription see).
- Duration: 720000 × 0.60 ÷ 200000 = 2.16 hours, so about 130 minutes.
If the target is 3 hours, repeat with the group of a total of 2000 Ah: Wh = 960000, C-ratio approx. 0.24, ratio 0.60. Duration = 960000 × 0.60 ÷ 200000 = approx 173 minutes.
For load analysis, see. UPS and Battery Capacity Project Design.

What is the maximum amount of battery connected to a 300 kVA UPS?
The number of batteries is fixed, the number of parallel strings is limited
Each array connects 240 2 V cells (480 V) in series. You cannot change this number. To extend the time, the cell Ah value is enlarged or a parallel array is added. At this power, three or more parallel strings are usually installed instead of a single string. The highest number of parallel strings in the manufacturer's data sheet and the total Ah limit must be observed. See What is a Battery String?.
Charging current is the most important limit
At this power, the charging current is not provided by a single circuit. The charging circuit of each UPS unit is collected or a separate charging rectifier is added. The exact value is in the data sheet.
Rule: Ah = charging current × 10 (comfortable) to 20 × (limit).
| Total charging current | Recommended maximum total battery (Ah) | Full charge time (roughly) |
|---|---|---|
| 100 A | 1000-2000 Ah | 12-24 hours |
| 200 A | 2000-4000 Ah | 12-24 hours |
| 400 A | 4000-8000 Ah | 12-24 hours |
| 800 A | 8000-16000 Ah | 12-24 hours |
Rough charging time: Ah × 1.2 ÷ charging current (hours). In the example above, a total charging current of 75-150 A is required for 1500 Ah, and 100-200 A for 2000 Ah.
DC current, busbar and protection
At full load, the total DC current is approximately 652 A. This current does not flow through a single string. Each string must have its own DC fuse and switch. Copper busbar cross-sections, short-circuit strength, and busbar distances require project engineering.
Weight, space and ventilation
A group of 2 V cells of 480 V weighs roughly 15 kg × Ah. For example, 1500 Ah holds about 22 tons, 3000 Ah about 45 tons. For these weights, the floor load and rack bearing capacity must be verified by static calculation before installation. Ventilation, temperature and fire safety are planned separately in the battery room. See Factors Affecting Battery Life.
Lithium option
If space and weight are a problem, a lithium battery is also an option. See Lithium-Ion UPS Batteries and What is Thermal Runaway? How to Prevent It in Batteries?. For 2 V cells, see V. What is OPzS and OPzV Battery?.
Security: 480 V DC is life-threatening. Battery addition, connection and insurance are the work of authorized personnel.
Is 300 kVA a single UPS or a system?
Instead of concentrating 300 kVA in a single unit, it is common to install two 150 kVA or three 100 kVA parallel systems. With N+1 redundancy, the load is carried even if one unit is missing. The modular structure allows for gradual capacity increases and live module replacement. See What is a Modular UPS?, What is Redundancy in UPS?, Parallel UPS Installation and Load Sharing and UPS Architecture in Data Centers.
Summary for all kVA classes on one page: How Long Does a UPS Work? kVA Guide
Frequently Asked Questions
01Will a 300 kVA UPS run for 1 hour?
02Is a battery room required for a 300 kVA UPS?
03Do I need a generator?
04How do I verify duration?