How Long Does a 300 kVA UPS Work? Duration Table and Calculation

How Long Does a 300 kVA UPS Work? Duration Table and Calculation

300 kVA UPS; It is used for large data centers, hospitals, airports and heavy industry facilities. At this power, DC current reaches 650 amps at full load. The battery system is a battery room with multiple strings and a separate engineering project. In this article, we explained the time table, calculation method and how many batteries can be connected to the system.

Short answer

The battery bank of a 300 kVA UPS system is usually 480 V DC (40 12 V blocks or 240 2 V cells). Some manufacturers use different voltages, such as 576 V. A single battery string is not enough at this power. Multiple strings are connected in parallel and the time is total Ah value determined accordingly. In this article, all times are given over the total Ah. Approximate times:

  • At full load (approx. 270000 W) with a total of 1000 Ah: approx. 51 minutes
  • At full load with a total of 1500 Ah: approx. 1 hour and 27 minutes
  • At half load (approx. 135000 W) with a total of 1500 Ah: approx. 3 hours 30 minutes
  • At full load with a total of 3000 Ah: approx. 3 hours 30 minutes

The calculations were made with 90% efficiency and 0.9 power factor. Since the efficiency of the new generation large UPSs is higher, the actual times may be a little longer. In most projects, the target time is 10-30 minutes. This time acts as a bridge until the generator is activated.

How many watts does a 300 kVA UPS carry?

  • In the system with a power factor of 0.9, 300 kVA is approximately 270000 W does.
  • In the new generation model with a power factor of 1,0 300000 W does.
  • In the old model with a power factor of 0.8 240000 W does.

The power factor is written in the data sheet. See What is Power Factor?.

Battery room with several 2 V cells arranged in long racks

Time table for 300 kVA UPS (480 V DC, total Ah)

Durations for new VRLA/AGM battery (2 V cell), 25 °C and 0.9 power factor and 90% UPS efficiency They are rough calculations. The actual time may deviate by 20-30% ± depending on the model. "Total Ah" is the sum of the Ah values of all 480 V arrays connected in parallel.

Total battery capacityFull load (270000 W)75% load (202500 W)Half load (135000 W)25% load (67500 W)
800 Ah38 min55 min1 hr 34 min3 hr 45 min
1000 Ah51 min1 hr 14 min2 hr 5 min4 hr 50 min
1500 Ah1 hr 27 min2 hr 5 min3 hr 30 min7 hr 45 min
2000 Ah2 hr 5 min3 h4 hr 50 min10 hr 40 min
3000 Ah3 hr 30 min4 hr 50 min7 hr 45 minOver 12 h

The calculation loses its reliability for periods above 12 hours. A generator solution is used for such a long time at this power.

Airport terminal operations center protected by UPS

Example calculation: 200000 W load at the airport

Terminal IT, baggage control system, security and emergency lighting at an airport draw a total of 200000 W. The UPS system has 480 V DC input, the total battery capacity is 1500 Ah.

  1. Battery energy: 480 V × 1500 Ah = 720000 Wh.
  2. Current: 200000 ÷ (0.9 × 40 × 11.5 V) = approximately 483 A (sum of all sequences).
  3. C-rate: 483 ÷ 1500 = approximately 0.32.
  4. Available rate: Since the C-ratio is between 0.2-0.5, 0.60 (for the ratio table 1 kVA inscription see).
  5. Duration: 720000 × 0.60 ÷ 200000 = 2.16 hours, so about 130 minutes.

If the target is 3 hours, repeat with the group of a total of 2000 Ah: Wh = 960000, C-ratio approx. 0.24, ratio 0.60. Duration = 960000 × 0.60 ÷ 200000 = approx 173 minutes.

For load analysis, see. UPS and Battery Capacity Project Design.

Technician checks bus connection between battery cells with insulating torque wrench

What is the maximum amount of battery connected to a 300 kVA UPS?

The number of batteries is fixed, the number of parallel strings is limited

Each array connects 240 2 V cells (480 V) in series. You cannot change this number. To extend the time, the cell Ah value is enlarged or a parallel array is added. At this power, three or more parallel strings are usually installed instead of a single string. The highest number of parallel strings in the manufacturer's data sheet and the total Ah limit must be observed. See What is a Battery String?.

Charging current is the most important limit

At this power, the charging current is not provided by a single circuit. The charging circuit of each UPS unit is collected or a separate charging rectifier is added. The exact value is in the data sheet.

Rule: Ah = charging current × 10 (comfortable) to 20 × (limit).

Total charging currentRecommended maximum total battery (Ah)Full charge time (roughly)
100 A1000-2000 Ah12-24 hours
200 A2000-4000 Ah12-24 hours
400 A4000-8000 Ah12-24 hours
800 A8000-16000 Ah12-24 hours

Rough charging time: Ah × 1.2 ÷ charging current (hours). In the example above, a total charging current of 75-150 A is required for 1500 Ah, and 100-200 A for 2000 Ah.

DC current, busbar and protection

At full load, the total DC current is approximately 652 A. This current does not flow through a single string. Each string must have its own DC fuse and switch. Copper busbar cross-sections, short-circuit strength, and busbar distances require project engineering.

Weight, space and ventilation

A group of 2 V cells of 480 V weighs roughly 15 kg × Ah. For example, 1500 Ah holds about 22 tons, 3000 Ah about 45 tons. For these weights, the floor load and rack bearing capacity must be verified by static calculation before installation. Ventilation, temperature and fire safety are planned separately in the battery room. See Factors Affecting Battery Life.

Lithium option

If space and weight are a problem, a lithium battery is also an option. See Lithium-Ion UPS Batteries and What is Thermal Runaway? How to Prevent It in Batteries?. For 2 V cells, see V. What is OPzS and OPzV Battery?.

Security: 480 V DC is life-threatening. Battery addition, connection and insurance are the work of authorized personnel.

Is 300 kVA a single UPS or a system?

Instead of concentrating 300 kVA in a single unit, it is common to install two 150 kVA or three 100 kVA parallel systems. With N+1 redundancy, the load is carried even if one unit is missing. The modular structure allows for gradual capacity increases and live module replacement. See What is a Modular UPS?, What is Redundancy in UPS?, Parallel UPS Installation and Load Sharing and UPS Architecture in Data Centers.

Summary for all kVA classes on one page: How Long Does a UPS Work? kVA Guide

Frequently Asked Questions

01Will a 300 kVA UPS run for 1 hour?
With a total group of 1500 Ah, you get about 3 hours and 30 minutes with a total group of 135000 Ah, and about 2 hours and 5 minutes with a group of 1000 Ah. For 1 hour at full load, a group of about 1100 Ah is required.
02Is a battery room required for a 300 kVA UPS?
Yes, as well as a large battery room. The rack requires ventilation, temperature control, fire safety, and floor bearing capacity.
03Do I need a generator?
If the goal is to run longer than 30 minutes at full load, the generator is almost always more economical. See Differences Between UPS and Generator.
04How do I verify duration?
The most reliable method is the discharge test. See Discharge and Load Tests.