How Long Does a 30 kVA UPS Work? Duration Table and Calculation

How Long Does a 30 kVA UPS Work? Duration Table and Calculation

30 kVA UPS; It is used for small factories, building automation, data rooms, hospital departments and critical office floors. At this power, the UPS is almost always three-phase and the battery pack consists of 32-40 12 V batteries. How many minutes or hours the UPS will work depends entirely on the size of the battery cabinet. In this article, we explained the time table, calculation method and the maximum amount of battery that can be connected to the UPS.

Short answer

The DC voltage of a 30 kVA UPS is usually 384 V (32 x 12 V batteries) or 480 V (40 x 12 V batteries). Refer to the label and data sheet for the number of batteries. Approximate times with a 384 V group:

  • At full load (approx. 27000 W) with 65 Ah batteries: 20-25 minutes
  • At full load with 100 Ah batteries: 35-40 minutes
  • At half load (approx. 13500 W) with 100 Ah batteries: approx. 1 hour 30 minutes
  • At half load with 200 Ah batteries: approx. 3 hours 45 minutes

The standard battery range at this power is between 65-200 Ah.

How many watts does a 30 kVA UPS carry?

  • A power factor of 0.9 in a UPS has a 30 kVA approx. 27000 W does.
  • In the new generation model with a power factor of 1,0 30000 W does.
  • In the old model with a power factor of 0.8 24000 W does.

The power factor is written in the data sheet. See What is Power Factor?.

Thirty-two 12V UPS batteries stacked in two-deck rack and connected in series

Time table for 30 kVA UPS (32 x 12 V batteries, 384 V DC)

Durations for new VRLA/AGM battery, 25 °C and 0.9 power factor and 90% UPS efficiency They are rough calculations. The actual time may deviate by 20-30% ± depending on the model.

Ah on each batteryFull load (27000 W)75% load (20250 W)Half load (13500 W)25% load (6750 W)
40 Ah11 min17 min29 min1 hr 10 min
65 Ah22 min32 min54 min2 hr 10 min
100 Ah38 min55 min1 hr 35 min3 hr 45 min
150 Ah1 hr 5 min1 hr 35 min2 hr 40 min6 h
200 Ah1 hr 35 min2 hr 15 min3 hr 45 min8 hr 20 min

On 480V (40 cord) version times are longer. For example, you get about 29 minutes at full load with 65 Ah batteries, about 51 minutes with 100 Ah batteries, and about 2 hours and 5 minutes with 200 Ah batteries. The reason is that less current is drawn from each battery. Therefore, the number of batteries is one of the questions to be asked when choosing a UPS.

Example calculation: 18000 W load in the plant

Servers, control panels, security systems and office load in a facility draw a total of 18000 W. UPS 384 V, there are 32 100 Ah batteries in the battery cabinet.

  1. Battery energy: 32 × 12 V × 100 Ah = 38400 Wh.
  2. Current: 18000 ÷ (0.9 × 32 × 11.5 V) = approximately 54.3 A.
  3. C-rate: 54.3 ÷ 100 = approximately 0.54.
  4. Available rate: Since the C-ratio is between 0.5-1, it is 0.50 (for the ratio table 1 kVA inscription see).
  5. Duration: 38400 × 0.50 ÷ 18000 = 1.07 hours, so about 64 minutes.

If you do the same calculation for 65 Ah, you can do about 42 min comes out. So 100 Ah is required for the 1 hour target.

Load analysis is essential for the correct sizing of the investment at this power. See UPS and Battery Capacity Project Design.

Factory control room protected by UPS

What is the maximum amount of battery connected to a 30 kVA UPS?

The number of batteries is fixed

32 batteries are connected in series for the 384 V model and 40 for the 480 V model 12 V batteries. You cannot change this number. To extend the time, switch to batteries with larger Ah or add parallel from the same array. The number of parallel strings is usually limited to 2-4. Refer to the manufacturer's data sheet. See What is a Battery String?.

Charging current is the most important limit

At this power, the charging current is usually around 10 A in standard models. In long-run models, it can be 20-40 A or above. The exact value is in the data sheet.

Rule: Ah = charging current × 10 (comfortable) to 20 × (limit).

UPS charging currentRecommended maximum battery (Ah)Full charge time (roughly)
10 A100-200 Ah12-24 hours
20 A200-400 Ah12-24 hours
30 A300-600 Ah12-24 hours
40 A400-800 Ah12-24 hours

Coarse charging time: Ah × 1.2 ÷ charging current (hours). For 100 Ah in the above plant example, 5-10 A is sufficient. For a group of 200 Ah, at least 10-20 A is recommended.

DC current, cable and protection

At full load, the DC current is approximately 82 A in the 384 V model and approximately 65 A in the 480 V model. At this level, the cable cross-section, DC fuse and switch selection should be made calculatedly. Insufficient cross-section leads to heating and loss of time.

Weight and area

32 12 V 100 Ah batteries hold approximately 900-1000 kg, 40 12 V 65 Ah batteries approximately 800 kg. Floor load, cabinet size, and ventilation should be checked before installation. See Lithium Battery Cabinet Installation: Layout, Ventilation, and Safety Distances (written for lithium, the principles of settlement are similar).

Highest Ah battery

The practical upper limit for single block 12 V batteries is around 200 Ah. Larger capacities use 2 V cells (OPzV/OPzS). See What is OPzS and OPzV Battery?.

Security: 384-480 V DC is life-threatening. Battery addition, cabin connection and fuse works are the work of authorized personnel.

Technician measuring current in DC cable of UPS battery pack with clamp meter

30 kVA UPS is three-phase

30 kVA UPSs are mostly 3 phase input, 3 phase output (3/3). Some models also have a 3/1 option. See Differences Between Three-Phase and Single-Phase UPS and Differences Between Transformered and Transformerless UPS.

Growth and redundancy

For critical loads, a parallel UPS (N+1) is preferred over a single UPS. If one fails, the other carries the load. See What is Redundancy in UPS? and Parallel UPS Installation and Load Sharing. If there is an expectation of growth Modular UPS is also an option.

Summary for all kVA classes on one page: How Long Does a UPS Work? kVA Guide

Frequently Asked Questions

01Will a 30 kVA UPS run for 1 hour?
At a load of up to 13500 W, you get about 54 minutes with 65 Ah batteries, and about 1 hour and 35 minutes with 100 Ah batteries. For 1 hour at full load, you need about 150 Ah per battery.
02How much space do the batteries of a 30 kVA UPS take up?
32 100 Ah batteries require a two-story rack or a large battery cabinet. Check the floor load before installation.
03Do I need a generator?
If there is a target of running longer than 1-2 hours at full load, the generator is often more economical. See Differences Between UPS and Generator.
04How do I verify duration?
The most reliable method is the discharge test. See Discharge and Load Tests.