TCMB foreign exchange selling rate · 25.11.2026: USD 50,64 ₺ EUR 55,40 ₺

How Long Does a 20 kVA UPS Work? Duration Table and Calculation

How Long Does a 20 kVA UPS Work? Duration Table and Calculation

20 kVA UPS; It is used for small data rooms, control systems of production lines, laboratories, building automation and critical office floors. At this power, 12 V batteries are connected in series of more than 30 units, and the battery cabinet is as big an investment as the UPS itself. In this article, we explained the time table, calculation method and how many batteries can be connected to the UPS.

Short answer

The DC voltage of a 20 kVA UPS varies depending on the model. For most three-phase models, it is around 360-480 V (30-40 x 12 V batteries). Some models have 240 V (20 batteries). Refer to the label and data sheet for the number of batteries. Approximate times for 384 V (32 batteries):

  • At full load (approx. 18000 W) with 26 Ah batteries: 10-12 minutes
  • At half load (approx. 9000 W) with 26 Ah batteries: 25-30 minutes
  • At half load with 65 Ah batteries: approx. 1 hour 30 minutes
  • At half load with 100 Ah batteries: approx. 2 hours 40 minutes

There is practically no work with small (7-9 Ah) batteries of this power.

How many watts does a 20 kVA UPS carry?

  • In a UPS with a power factor of 0.9, 20 kVA is approximately 18000 W does.
  • In the model with a power factor of 1.0 20000 W does.
  • In the old model with a power factor of 0.8 16000 W does.

The power factor is written in the data sheet. See What is Power Factor?.

Thirty-two 12V UPS batteries racked in three tiers and connected in series

Time table for 20 kVA UPS (32 x 12 V batteries, 384 V DC)

Durations for new VRLA/AGM battery, 25 °C and 0.9 power factor and 90% UPS efficiency They are rough calculations. The actual time may deviate by 20-30% ± depending on the model.

Ah on each batteryFull load (18000 W)75% load (13500 W)Half load (9000 W)25% load (4500 W)
26 Ah11 min16 min28 min1 hr 10 min
40 Ah20 min29 min48 min2 h
65 Ah37 min54 min1 hr 30 min3 hr 40 min
100 Ah1 hr 5 min1 hr 35 min2 hr 40 min6 h
150 Ah1 hr 50 min2 hr 40 min4 hr 20 min9 hr 30 min
200 Ah2 hr 40 min3 hr 45 min6 hOver 12 h

On 240V (20 cord) version times are much shorter. For example, you get about 6 minutes at full load with 26 Ah batteries, about 20 minutes with 65 Ah batteries, and about 35 minutes with 100 Ah batteries. Because more current is drawn from each battery. Therefore, a high-voltage UPS with the same Ah value gives a longer time.

Server rack rows in data room protected by UPS

Example calculation: 12000 W load in data room

In a data room, servers, storage, network devices and control equipment draw a total of 12000 W. The UPS is 384 V, there are 32 65 Ah batteries in the battery cabinet.

  1. Battery energy: 32 × 12 V × 65 Ah = 24960 Wh.
  2. Current: 12000 ÷ (0.9 × 32 × 11.5 V) = approximately 36.2 A.
  3. C-rate: 36.2 ÷ 65 = approximately 0.56.
  4. Available rate: Since the C-ratio is between 0.5-1, it is 0.50 (for the ratio table 1 kVA inscription see).
  5. Duration: 24960 × 0.50 ÷ 12000 = 1.04 hours, so about 62 minutes.

If the goal is 30 minutes, also look with 40 Ah batteries: Wh = 15360, C-ratio approx. 0.9, ratio 0.50. Duration = 15360 × 0.50 ÷ 12000 = approx 38 min. So 40 Ah is enough for the 30-minute target.

Technician in insulating gloves checking DC fuse and switch in battery cabinet

What is the maximum amount of battery connected to a 20 kVA UPS?

The number of batteries is fixed

Depending on the model, the DC voltage is generated by connecting 20, 30, 32 or 40 12 V batteries in series. You cannot change this number. To extend the time, you can switch to batteries with larger Ah or add parallel from the same string. The number of parallel strings is usually limited to 2-4. Refer to the manufacturer's data sheet. See What is a Battery String?.

Charging current is the most important limit

At this power, the charging current is between a few and 10 A in standard models. In long-run models, it can be 20 A or more. The exact value is in the data sheet.

Rule: Ah = charging current × 10 (comfortable) to 20 × (limit).

UPS charging currentRecommended maximum battery (Ah)Full charge time (roughly)
4 A40-80 Ah12-24 hours
8 A80-160 Ah12-24 hours
12 A120-240 Ah12-24 hours
20 A200-400 Ah12-24 hours

Coarse charging time: Ah × 1.2 ÷ charging current (hours). For 65 Ah in the data room example above, 4-6 A is sufficient. For a group of 200 Ah, at least 10 A is recommended.

DC current, cable and protection

At full load, the DC current is approximately 54 A in the 384 V model and approximately 87 A in the 240 V model. 87 A requires serious calculation in cable cross-section and DC fuse selection. Therefore, structures with high voltage (384 V and above) at 20 kVA are preferred.

Weight, space and ventilation

32 12 V 65 Ah batteries hold approximately 610-670 kg. Floor load, cabinet size, and ventilation should be checked before installation. Battery rooms require ventilation to prevent hydrogen build-up. See Lithium Battery Cabinet Installation: Layout, Ventilation, and Safety Distances (written for lithium, the principles of settlement are similar).

Highest Ah battery

The practical upper limit for single-block 12 V batteries is around 200 Ah. At this level, 2 V cells (OPzV/OPzS) and lithium solutions come to the fore. See What is OPzS and OPzV Battery? and Lithium-Ion UPS Batteries.

Security: 360-480 V DC is life-threatening. Battery addition, cabin connection and insurance are the work of authorized personnel.

How do you plan to grow at 20 kVA?

Summary for all kVA classes on one page: How Long Does a UPS Work? kVA Guide

Frequently Asked Questions

01Does a 20 kVA UPS run for 1 hour?
With 65 Ah batteries at a load of up to 9000 W, you get about 1 hour and 30 minutes. For 1 hour at full load, you need about 100 Ah per battery.
02Should a 20 kVA UPS be three phase?
Most 20 kVA UPS have a three-phase input (3/1 or 3/3). See Differences Between Three-Phase and Single-Phase UPS.
03How many years do batteries last?
Usually 3-5 years. See What is the Lifespan of a UPS?.
04How do I verify duration?
The most reliable method is the discharge test. See Discharge and Load Tests.

Let's Choose the Right UPS Together

Bempower https://www.bemenerji.com/en/blog/how-long-does-a-20-kva-ups-work-duration-table-and-calculation
Write via WhatsApp