How Long Does a 10 kVA UPS Work? Duration Table and Calculation

How Long Does a 10 kVA UPS Work? Duration Table and Calculation

10 kVA UPS; It is the power frequently chosen for server rooms, small clinics, workshops and multi-computer offices. At this power, the issue of duration is no longer a matter of "battery inside". Most 10 kVA UPS are sold without batteries and the external battery cabinet determines the duration. In this article, we explained the duration table, calculation method and the maximum amount of battery that can be connected to the battery cabinet.

Short answer

Most 10 kVA online UPS have 16 12 V batteries connected in series (192 V DC). Some models use 20 batteries (240 V). Approximate times with small 9 Ah batteries:

  • 192 V (16 batteries), full load (approx. 9000 W): 2-4 minutes
  • 192 V, half load (approx. 4500 W): 6-8 minutes
  • 240 V (20 batteries), full load: 3-5 minutes

These times are very short. Therefore, models with small batteries of 10 kVA and above are only suitable for safe switching. If minutes of operation are required, an external cabinet is used with batteries of 26-100 Ah.

How many watts does a 10 kVA UPS carry?

  • In a UPS with a power factor of 0.9, 10 kVA is approximately 9000 W does.
  • In the model with a power factor of 1.0 10000 W does.
  • In the old model with a power factor of 0.8 8000 W does.

The power factor is written in the data sheet. See What is Power Factor?.

Battery pack arranged on shelves inside the battery cabinet with open lid

Time table for 10 kVA UPS (16 x 12 V batteries, 192 V DC)

Durations for new VRLA/AGM battery, 25 °C and 0.9 power factor and 90% UPS efficiency They are rough calculations. The actual time may deviate by 20-30% ± depending on the model.

Ah on each batteryFull load (9000 W)75% load (6750 W)Half load (4500 W)25% load (2250 W)
9 Ah3 min4 min7 min17 min
17 Ah6 min9 min16 min39 min
26 Ah11 min16 min28 min1 hr 10 min
40 Ah20 min29 min48 min2 h
65 Ah37 min54 min1 hr 30 min3 hr 40 min
100 Ah1 hr 5 min1 hr 35 min2 hr 40 min6 h

On 240 V (20 batteries) models, the times are longer with the same batteries. For example, with 26 Ah batteries you get about 15 minutes at full load, with 65 Ah batteries about 50 minutes. This is because less current is drawn from each battery.

Rack cabinets in server room protected by UPS

Example calculation: 6000 W load in server room

In a server room, the servers, storage, switch and cooling control unit draw a total of 6000 W. The UPS is 192 V, there are 16 40 Ah batteries in the battery cabinet.

  1. Battery energy: 16 × 12 V × 40 Ah = 7680 Wh.
  2. Current: 6000 ÷ (0.9 × 16 × 11.5 V) = approximately 36.2 A.
  3. C-rate: 36.2 ÷ 40 = approximately 0.9.
  4. Available rate: Since the C-ratio is between 0.5-1, it is 0.50 (for the ratio table 1 kVA inscription see).
  5. Duration: 7680 × 0.50 ÷ 6000 = 0.64 hours, so about 38 min.

If the goal is 1 hour, repeat with 65 Ah batteries: Wh = 12480, C-ratio approx. 0.56, ratio 0.50. Duration = 12480 × 0.50 ÷ 6000 = approx 62 minutes.

Load analysis is essential to target the duration realistically. See UPS and Battery Capacity Project Design and How to Calculate the Cost of a Power Outage to the Business?.

Technician measuring current in battery cabinet cable with clamp meter

What is the maximum amount of battery connected to a 10 kVA UPS?

The number of batteries is fixed

16 16 V batteries are connected in series for the 192 V model and 20 12 V batteries for the 240 V model. You cannot change this number. There are two ways to extend the time: switch to larger Ah batteries or add a parallel array of the same number of batteries. Manufacturers usually limit the number of parallel strings to 2-4. See the data sheet for the limit. For series-to-parallel rules What is a Battery String? See the article.

Charging current is the most important limit

At this power, the charging current in standard models is usually a few amperes. In long-run models, it can be 10-20 A or above. The exact value is in the data sheet.

Rule: Ah = charging current × 10 (comfortable) to 20 × (limit).

UPS charging currentRecommended maximum battery (Ah)Full charge time (roughly)
4 A40-80 Ah12-24 hours
8 A80-160 Ah12-24 hours
12 A120-240 Ah12-24 hours
20 A200-400 Ah12-24 hours

Rough charging time: Ah × 1.2 ÷ charging current (hours). For 65 Ah in the server room example above, a charging current of 4-6 A is sufficient.

DC current, cable and protection

At full load, the DC current is approximately 54 A in the 192 V model and approximately 44 A in the 240 V model. The cable, fuse and DC switch between the battery cabinet and the UPS must carry this current easily. Incorrect cable cross-section at this level leads to both loss of time and heating.

Battery cabinet, weight and space

16 12 V 65 Ah batteries hold approximately 300-340 kg. Floor load, cabinet size, and ventilation should be checked before installation. See Lithium Battery Cabinet Installation: Layout, Ventilation, and Safety Distances (written for lithium, the principles of settlement are similar).

Highest Ah battery

The practical upper limit for single block 12 V batteries is around 200 Ah. Larger capacities use 2 V cells (OPzV/OPzS). See What is OPzS and OPzV Battery?.

Security: 192-240 V DC poses a live hazard. Battery addition, cabin connection and fuse work should be left to authorized personnel. See Can Every Battery Be Installed in Every UPS?.

Single UPS or parallel at 10 kVA?

For jobs that cannot tolerate interruption, it is safer to run two UPSs in parallel (N+1) rather than a single 10 kVA. If one fails, the other bears the load. See What is Redundancy in UPS? and Parallel UPS Installation and Load Sharing.

Summary for all kVA classes on one page: How Long Does a UPS Work? kVA Guide

Frequently Asked Questions

01Does a 10 kVA UPS work for 30 minutes?
At a load of up to 4500 W, you get about 28 minutes with 26 Ah batteries. For 30 minutes at full load, you need about 65 Ah per battery.
02Can a 10 kVA UPS have a battery in it?
Some models come with a built-in battery, but the time is short. For a long time, the model without the battery and the external battery cabinet are chosen.
03How many Ah batteries are suitable for 10 kVA?
Between 26-100 Ah according to the duration target. If the charging current is not sufficient, the large battery will not be filled. Refer to the table above.
04What is the lifespan of batteries?