Differences Between UPS and Generator: Which, When, Together?
"We have a generator, do we need a UPS?" or vice versa, "We bought a UPS, is a generator necessary?" is one of the most frequently asked questions when planning backup power. Both are there to supply loads when the power goes out, but they do so in very different ways. In critical facilities, they are often used together, not in place of one.
Key Difference: Stored Energy vs. Energy Generated
UPSworks with the energy stored in its batteries. In an online UPS, since the inverter is already running continuously, the interruption is not reflected in the load at all; but the operating time is limited by the battery capacity. Internal structure How UPS works We explained it in the article.
Generator produces energy by burning fuel; it continues to work as long as the fuel is detected. However, after the interruption is detected, it takes time for the engine to start, the speed and voltage to settle and the load to be transferred. This time varies depending on the settings and the generator; it can range from roughly a few seconds to around half a minute. Meanwhile, the loads remain unsupplied.
Side-by-Side Comparison
| Feature | UPS | Generator |
|---|---|---|
| Engaging | Instant (no passes in online UPS) | seconds; no load supply at that time |
| Operating time | Depends on battery capacity; minutes most of the time | Fuel quite; hours, days |
| Output quality | Voltage and frequency in online UPS are off-grid | Voltage and frequency temporarily deviate in sudden load change |
| Suitable load | Server, network, automation, medical device | Lighting, air conditioning, pump, elevator and the whole building |
| Installation location | Closed, cool and airy space | Exhaust, noise, fuel tank; often outdoors |
| Care | Battery measurements, fan, capacitor, cleaning | Oil, filter, fuel, starter battery and regular test run |
Which one, when?
- UPS only: If the outages are short-lived, or the goal is to buy enough time to properly shut down the servers during the long outage.
- Generator alone: In loads where a few seconds of darkness is not a problem, but work stops after hours of downtime; for example, lighting, cooling and pumps.
- Together: Both in loads that cannot tolerate interruption for a moment and need to work for a long time; such as data center, hospital, production facility.
When Used Together, UPS Becomes a Bridge
In a system working together, events develop in the following order in the event of an outage: The UPS starts to feed the load from the battery; the generator starts, the voltage and frequency settle; ATS (automatic transfer switch) It transfers the panel to which the UPS is connected from the mains to the generator; the UPS starts feeding from the generator and recharges the batteries. When the mains returns, the ATS returns the panel to the mains after a set waiting period (during this short transfer, the UPS feeds it from the battery again) and the generator stops with a cool-down run.
In this setup, the UPS's batteries must comfortably cover the generator's activation time in the worst condition, such as when the first start attempt fails. However, considering what happens if the generator doesn't start, it's common to leave enough room to shut down the servers properly.
What does ATS do?
The ATS continuously monitors the grid, commands the generator to work in the event of an outage, and transfers the load between the two sources. There is a lockout that prevents two sources from being connected to each other at the same time. Transition and return delays can be adjusted; incorrect setting can lead to unnecessary transients or load failure to supply longer than expected.
Generator and UPS Compatibility
The voltage and frequency of the generator are not as stable as the mains: when a large load is connected or disconnected, it deviates for a while, then re-settles. This can have two consequences on the UPS side:
- Input tolerance: If the voltage or frequency is outside the range accepted by the UPS, the UPS will not accept the generator and will continue to work from the battery. If this is prolonged, the batteries may discharge while the generator is running.
- Bypass synchronization: The inverter monitors its frequency to stay compatible with the bypass line. As the frequency of the generator fluctuates, the fit may be lost; in this case, a seamless transition to bypass is not possible. Detail What is UPS bypass in his article.
In many UPSs, the input interval, synchronization window and the rectifier load gradual retrieval time can be adjusted. These settings are made according to the behavior of the generator by trying them together during commissioning.
How to Choose Generator Power?
The generator is not selected based on the output power on the UPS label. The UPS draws the load from the input, its own losses and the battery charge together; the generator also carries other loads in the building, the starting currents of the motors and the harmonics. For this reason, manufacturers and project developers often estimate generator power as a share above the UPS power. The amount of the share depends on the input characteristics of the UPS, the structure of the generator and other loads; it is determined by the recommendations of the UPS and generator manufacturer. Effect of input harmonics What is the power factor You can find it in the article.
Testing the System
The real test of a system that works together is not the moment the grid goes down, but the regular tests. Running the generator under load, testing ATS transitions and returns, and monitoring whether the UPS accepts the generator reveal problems before an actual outage. These tests are carried out at a scheduled time and Authorized Technical Personnel must be done by; it is not recommended for the user to take action on dashboards and ATS.
The system that works together at a glance
How the UPS and generator complement each other and the points to be considered when working together are summarized below.
The UPS becomes the bridge until the generator is activated; the generator also covers the long outage that the batteries will not suffice. Compliance is verified at commissioning and regular testing.
Frequently Asked Questions
01We have generator, do I still need UPS?
02How long should UPS batteries last?
03Why does the UPS continue to run from the battery when switching to the generator?
04Can we choose the generator the same as the UPS power?
05How often should we test the system?
Technical Support for UPS, Generator and ATS
In addition to UPS of all brands and models, we also perform fault detection, repair, operation and failover tests on generator and ATS systems; Fault detection in Istanbul is free of charge. Details Fault Detection and Technical Service on our page. For the installation and commissioning of the UPS UPS Installation and Assembly You can browse our page, information about your system You can send us.