Differences Between UPS and Regulator (Voltage Regulator)

Differences Between UPS and Regulator (Voltage Regulator)

In a place where voltage drops or rises frequently, most people think of the regulator first. But a regulator and a UPS don't do the same job: one corrects the voltage, and the other continues to supply the load when the power goes out completely. The wrong choice leads to either a system that stops in downtime or an unnecessary investment.

What Does a Regulator Do?

The voltage regulator keeps the output voltage close to the rated value while the mains voltage varies within a certain range. It raises the voltage when it drops and lowers it when it rises. However:

  • Does not feed in interruption: There is no battery inside; when the power goes out, the output is also cut off.
  • Does not correct frequency: The output frequency is the same as that of the network.
  • Its range is limited: If the input voltage goes out of the regulator's range, the output also goes out of boundary, or the protection circuit cuts off the output.
  • Shock and noise protection varies by model: Some models have additional filter and surge protection, some do not.

The capacity of the impact protection elements in regulators and UPSs is limited. A surge arrester (surge protection device) is also planned in the panel for high-energy pulses coming from lightning or switching in the network.

Types of Regulators

TypeHow does it work?Feature
RelayIt passes between the stages of the transformer with relaysEconomic; correction gradual, there may be a short deviation in the transition
Servo motorA motor slides the brush of the tuned transformerStepless and sensitive; its response is relatively slow, it catches sudden changes late
Static (electronic)In most designs, the stages are replaced with semiconductor switchesNo moving parts, fast response

Which type is appropriate is determined by how much and how quickly the voltage changes and the load being supplied. A regulator is also a power device; it heats up under load, its power must be chosen to meet the load's inrush currents. The power that many regulators can deliver decreases as the input voltage drops; this is also taken into account in the selection.

AVR in Line-Interactive UPS

Inside the line-interactive UPS, there is actually a regulator that looks like a relay AVR (automatic voltage regulation) circuit. When the voltage drops or rises, the UPS first corrects it with AVR stages; if the correction is not enough or the power is cut off, it switches to the battery. In other words, the line-interactive UPS does what a regulator does and adds the battery supply in case of an outage.

The difference is that there is a transition of a few milliseconds in the outage, the frequency is again connected to the mains. Where the voltage often goes out of the AVR range, the UPS switches to the battery very often and the batteries wear out more quickly.

Online UPS: Beyond the Regulator

In an online (double conversion) UPS, the incoming energy is first converted into direct current, and then the inverter produces a new and smooth sine. Both the output voltage and frequency are independent of the grid; voltage drops, rises and frequency deviations do not reach the load. Although the input voltage varies over a wide range, the UPS can operate without switching to the battery; the limits of the range are written in the technical sheet and in most models they also vary according to the load ratio. Internal structure How UPS works We explained step by step in the article; For a comparison of the three types of UPS Types of UPS You can take a look at the article.

Comparison

FeatureRegulatorLine-interactive UPSOnline UPS
Voltage correctionThere isYes (AVR)Continuous, off-grid
Frequency correctionNoneNoneThere is
Feed on interruptionNoneYes; with a short passageYes; intransitive
Battery maintenanceNoneThere isThere is
Typical useMotorized appliance, machinery, air conditioner, household appliancesOffice computer, network deviceServer, medical device, automation

In Which Situation?

  • Tension fluctuates, the outage is infrequent, the load is not affected by a short outage: The regulator may be sufficient; for example, workshop machines and heating, cooling devices.
  • Outage leads to data loss or business downtime: UPS is required; the regulator does not solve this problem.
  • The grid is both fluctuating and intermittent, load sensitive: Online UPS. A separate regulator is often not needed to correct the voltage.
  • Large motorized loads: It is often not economical to connect them to the UPS due to the inrush currents; in these loads, a regulator or generator is considered. Comparison with generator The difference between UPS and generator You can find it in the article.

Do I Need a Regulator When You Have a UPS?

It is usually not necessary to put a regulator in front of an online UPS. In line-interactive UPSs, if the voltage goes out of range too often, continuous operation of the batteries may be a problem; in this case, first measuring in the network, then switching to the online UPS or a regulator at the entrance are evaluated together. Short voltage jumps created by step-down regulators when changing levels can unnecessarily switch line-interactive UPSs to the battery; therefore, the compatibility of the two devices should be tested in the field.

The source of the voltage drop is sometimes the building itself: thin or long cables, loose connections, overloaded phases. The regulator or UPS hides this problem, but does not eliminate it. Measurements and connections to the cabinet Authorized Technical Personnel It should be done by.

Regulator, AVR and Online UPS

What the three solutions do against voltage surge and power failure is summarized below.

Only a regulator is needed if there is a voltage problem, and a UPS is needed if an outage affects your business. For sensitive loads and a fluctuating network, an online UPS covers both.

Frequently Asked Questions

01Will the regulator protect my devices in case of a power outage?
The regulator does not have a battery; when the power goes out, the output is also cut off. A UPS is required to maintain power supply during an outage.
02Is a line-interactive UPS a substitute for a regulator?
Since it corrects voltage fluctuations with AVR, it keeps it at most small loads. However, if the voltage goes out of range very often, the UPS will often switch to the battery and the batteries will wear out faster; in this case, an online UPS may be more suitable.
03Should I install a regulator in front of an online UPS?
Usually not required; online UPS works in a wide input range without switching to the battery and its output is independent of the mains. In places where the voltage goes beyond this range, measurement should be made first.
04Which is suitable for a refrigerator or air conditioner?
These motorized devices are usually not damaged by a short interruption and draw high current when starting off. If there is only a voltage problem, a regulator of appropriate power is often a more economical solution.
05Why is the voltage constantly low?
It may be caused by the network itself, as well as thin or long cables, loose connections or unevenly loaded phases in the building. Measurement on the panel should be done by authorized technical personnel.

Let's Choose the Right Protection Together

Approximate power of the devices to be fed Power Calculation You can see it with our vehicle. We install and commission UPS of all brands and models throughout Istanbul and in the surrounding provinces; process UPS Installation and Assembly We explained it on our page. The voltage problem you are experiencing and your device list Send usLet's determine the solution that suits your needs together.