UPS and Battery Systems in Hospitals

UPS and Battery Systems in Hospitals

A power outage in an office often results in lost productivity; in a hospital, however, it can directly affect patient safety. For this reason, power continuity in hospitals is not planned around a single device but rather involves the power grid, a generator, a UPS, and the wiring that connects them.

In this article, we provide an overview of the role of UPS and battery systems in hospitals, which loads are powered by the UPS, and how the system is maintained.

What Are the Consequences of a Power Outage at a Hospital?

  • Patient safety: Even a brief interruption can pose a risk to patients on life support or undergoing a procedure.
  • Medical devices: Some devices shut down during a power outage and may require calibration or adjustment upon restart; recordings and measurements may be interrupted.
  • Information systems: Patient records, laboratory and imaging systems, servers, and network devices will stop working; data on servers that do not shut down properly may become corrupted.
  • Lighting and communication: Hallways, escape routes, nurse call systems, and security systems must continue to function even during an outage.

Generators and UPS Systems Work Together

Generators cover long power outages in hospitals; however, it takes a few seconds for the generator to start up, stabilize the voltage, and transfer the load. Loads that cannot withstand this delay are powered by a UPS: when a power outage begins, the UPS switches to battery power; once the generator kicks in, the UPS draws power from the generator and recharges its batteries. The details of this transition The Difference Between a UPS and a Generator We explained this in our article.

The runtime of UPS batteries is selected so that it comfortably covers the generator’s startup time under the worst-case conditions and, in addition, allows time for a proper shutdown or intervention if the generator fails to start. The logic behind the calculation How is battery life calculated? You can find it in our article.

Which Loads Are Powered by a UPS?

Load groupWhy a UPS?
Critical medical devicesEven a brief interruption during the switchover to the generator can affect the device's operation.
Areas such as operating rooms and intensive care unitsThe power supply must not be interrupted while the process and monitoring are in progress.
Hospital information system and serversAccess to records must be maintained, and data loss must be prevented.
Nurse Call and CommunicationThe bond between the patient and the staff must not be broken.
Security systemsThe camera, card-based access system, and alarm system must continue to function even during a power outage.
Part of the emergency lighting systemVisibility must be maintained in critical areas; emergency lighting for escape routes is often provided separately by battery-powered fixtures or a central battery system.

This table provides a general overview. It shows which area and which device will receive which power supply Electrical Project and Related Regulations specify; the device manufacturer’s documentation is used as the basis for determining how medical devices should be powered. The general principle of isolating critical loads What is a critical load? We explained this in our article.

Separate Rules for Medical Facilities

There are specific rules for electrical installations in medical facilities that go beyond general installation codes; at the international level, these are IEC 60364-7-710 is addressed in accordance with the standard. The classification of spaces, the layout of the safety power supply, and additional protective measures are specified within this framework in the hospital’s electrical design.

The design and modification of this system are the responsibility of the engineers in charge of the project. The role of the UPS service is to ensure that the UPS and battery systems included in the project operate as expected, and to monitor and report on their performance.

Redundancy: Is a Single UPS Enough?

For a critical load connected to a single UPS, a failure or maintenance of that UPS poses a risk. For this reason, in critical areas, UPS systems operating in parallel, with redundant modules (N+1) or dual-power-source (2N) configurations, are considered. The differences between them UPS Redundancy: N+1, 2N, and Parallel UPS We explained this in our article. To ensure that maintenance can be performed without shutting down the loads, the use of the maintenance bypass and the redundant system is also planned from the outset.

Maintenance and Testing

As a general guideline, maintenance is recommended every three months for critical systems. Our Gold plan includes 4 visits per year, one discharge test per year, and a thermal camera inspection at each visit; our Platinum plan includes 8 visits per year, two discharge tests per year, on-site intervention within 2 hours in case of a failure, and 24/7 support. How the frequency is determined UPS Maintenance Frequency, contract items UPS Maintenance Contract You can find it in our article.

  • Discharge test: Displays the actual runtime of the batteries; a backup power supply is planned for critical loads. Details battery discharge test in our article.
  • Generator–UPS compatibility test: The generator's operation, the ATS switchover, and whether the UPS accepts the generator are all tested together at a scheduled time.
  • Thermal control: Loose connections and hot spots are detected before a failure occurs.

The tests were conducted in collaboration with the hospital's technical department, with load conditions and a backup power supply prepared, qualified technical staff is performed by [name]. It is not recommended that the user perform any operations on the control panel, ATS, or battery.

Battery Age and Reporting

The installation dates of battery banks, as well as the voltage and internal resistance values per battery recorded during each visit, must be documented. Tracking changes in these values over the years allows for planning ahead of any outages; signs of When should a UPS battery be replaced? We explained this in our article.

Reports should be readily available to the technical team and auditors. In our maintenance plans, a detailed report for each visit is stored on your "My Account" page; how to read the report How to Read a UPS Maintenance Report You can find it in our article.

  1. IEC 60364-7-710 — Low-voltage electrical installations: Medical locations
  2. IEC 62040-3 — Uninterruptible Power Systems (UPS), Part 3: Method for Specifying Performance and Test Requirements
  3. Product manuals and data sheets from UPS and battery manufacturers (specifications vary by manufacturer)

Sources

UPS in the Hospital: At a Glance

In hospitals, it is a link in a chain that works in conjunction with UPS systems, generators, and electrical installations; each link in the chain is planned and monitored separately.

The topics at the top determine how the system is set up, while those at the bottom determine how it is maintained over the years. Details on each topic are provided later in the article.

Frequently Asked Questions

01If the hospital has a generator, why is a UPS necessary?
It takes just a few seconds for the generator to start up and take over the load. Medical devices, information systems, and communication systems—which cannot withstand this brief interruption—are powered by a UPS; the UPS acts as a bridge until the generator kicks in.
02Can the entire hospital be powered by a UPS?
Generally, no, and it’s not necessary. A UPS is used for loads that cannot withstand a power outage; the generator supplies power to most of the lighting, as well as loads such as cooling systems and pumps. The electrical design specifies which loads receive which power source.
03Can we connect a medical device to any UPS?
Before connecting the device, the manufacturer’s documentation and the hospital’s electrical plans must be reviewed. The power supply for medical devices is planned by authorized personnel in accordance with these documents and relevant regulations.
04How often should hospital UPS systems be maintained?
The general approach for critical systems is maintenance every three months. Depending on the age of the batteries, environmental conditions, and frequency of outages, more frequent visits are scheduled if necessary; the actual service life of the batteries is verified through regular discharge tests.
05How do you verify compatibility between a generator and a UPS?
A scheduled power outage is simulated; the generator’s operation, the ATS switchover, and whether the UPS accepts the generator are monitored. The test is conducted by authorized technical personnel in collaboration with the hospital’s technical department.

Maintenance Plan for Your Critical Systems

We provide periodic maintenance for UPS and battery systems of all makes and models throughout Istanbul and the surrounding provinces. The scope of a maintenance visit Periodic Battery and UPS Maintenance On our website, all plans—including the Gold plan with four visits per year and the Platinum plan with eight visits per year— Maintenance Plans You can find them on our website. The brands and models of your UPS units, battery information, and the loads they power Please let us know; After the initial assessment, let’s work together to determine the plan that’s right for your system.