Solar Energy Monitoring Systems: Remotely Tracking Production and Battery Status
Once a solar energy system is installed, the biggest question for most users is this: Is the system really producing the expected energy, are the batteries full, is there a problem? A monitoring system is the tool that answers this question without a site visit and without guesswork. It records data from the PV array to the inverter output, from grid exchange to battery charge level, and generates alarms when needed.
In this guide, we go step by step through the components of a monitoring system, what each piece of data means, how the performance ratio (PR), which measures production quality, is calculated, why the battery state-of-charge percentage can sometimes be misleading, and how to set up alarms. The article is written for homeowners and country house users, small business owners, technical managers, and purchasing departments.
If you are not yet familiar with the basic components of the system, you may first look at the article explaining how a solar energy system works Here, our focus is monitoring the health of an installed system through data.
What is a solar energy monitoring system and why is it necessary?
A monitoring system consists of sensors, the inverter's or charge controller's own measurements, a data logger, and an interface where the data is displayed. Standards define this task more broadly: IEC 61724-1 specifies the equipment, methods, and terminology for photovoltaic system performance monitoring. The purposes of a monitoring system include observing performance trends, locating potential faults, and comparing the system against design expectations.
In practice, monitoring answers three questions:
- Is production normal? A comparison is made with yesterday, last week, and last year under the same weather conditions.
- Is the battery healthy? Charge level, voltage, current, temperature, and protection warnings are monitored.
- Has something changed? Sudden zero production, loss of connection, or gradually declining efficiency is noticed early.
The value of monitoring shows up especially with silent faults. A blown string fuse or a shaded group of panels does not stop the system; it only reduces production. Without data, this loss may go unnoticed for months. The U.S. Department of Energy's operations and maintenance guide also recommends that monitoring systems be able to report hourly, daily, monthly, and annual production, and that two key indicators (performance ratio and availability) be checked regularly during maintenance.

What is monitored? Production, consumption, and battery data
Monitoring platforms offer dozens of parameters; not all are equally important. The table below summarizes the key data that will be useful at home and small business scale.
| Data | What it tells you | Points to watch |
|---|---|---|
| DC array voltage and current | Instantaneous state of the PV array | A current noticeably lower than similar strings may indicate shading, dirt, or a connection problem |
| AC output power and energy (kWh) | Energy produced by the inverter | The intraday curve is expected to be a smooth bell shape; sudden notches are a sign of shading or an outage |
| Grid import/export | How much is drawn from or fed to the grid | If grid draw continues while production is high, the load and settings should be reviewed |
| Load consumption | The actual needs of the home or facility | The most valuable data for verifying battery sizing |
| Battery state of charge (SOC) | Estimated percentage of stored energy | If it consistently ends the night very low, there is a capacity or load problem |
| Battery voltage and current | Charge/discharge direction and intensity | If charge voltage does not match the set values, the charge profile should be checked |
| Battery temperature | Safety and lifespan | Temperatures outside the manufacturer's limits may restrict charging |
| Inverter temperature and error codes | Device health | The same code recurring may point to a persistent cause |
On the battery side, looking at the percentage alone is not enough. Information on how battery voltage is measured and interpreted gives a healthy picture when read together with current and temperature. If you want to see the charging stages (bulk, absorption, float) on the monitoring screen, the article on battery charge settings explains which voltages are expected.
How do monitoring systems work? Data path and connection options
Data usually flows through the following chain: the inverter or charge controller takes the measurement, a communication module or external data logger collects this data, sends it to a cloud server over a local network or cellular line, and the user views it from a browser or phone app. In systems with batteries, data from the BMS (battery management system) generally joins this chain through the inverter. We explained what the BMS does in a separate article
Common connection methods
| Method | Advantage | Limitation |
|---|---|---|
| Built-in inverter Wi-Fi / Ethernet module | Easy to install, usually compatible with the manufacturer's portal | If the Wi-Fi signal is weak, disconnections occur; the data depends on the manufacturer's system |
| External data logger (RS485 / Modbus, etc.) | Can aggregate multiple devices and keep local records | Requires correct protocol and address settings; wiring inside the panel must be done by authorized personnel |
| Energy meter + current sensor | Measures grid and load data independently | The sensor direction and phase must be installed correctly |
| Cellular (GSM/LTE) modem | Works at sites without internet | Line and data fees, coverage area |
| Your own server on the local network | The data belongs to you, with little cloud dependence | Installation and security management are your responsibility |
Two practical rules help when choosing. First, find out who stores the data and whether you will still have access to it if the device's cloud service is discontinued. Second, verify from the manufacturer's documentation whether the device stores data internally when the internet is cut and sends it later; otherwise, data from outage periods may be lost permanently.

The hybrid inverters' own measurements and communication features already form the backbone of monitoring; learning how a hybrid inverter works helps you understand which data will come from the device. For the UPS-side counterpart of remote monitoring and alarm management, see UPS remote monitoring and SNMP network card ; the network and alarm logic are largely similar.
What is the performance ratio (PR) and how is it calculated?
Looking only at kWh to judge whether production is "good" is misleading, because a cloudy day yields low production and a sunny day yields high production. The performance ratio (PR) normalizes this difference. According to IEC 61724-1, PR is the ratio of the system's final yield to its reference yield and shows the effect of total losses. In Sandia's definition, daily AC PR is the ratio of the yield obtained by dividing the measured AC energy by the rated power to the reference yield.
Example calculation (assumptions stated)
- Installed DC power: 5 kWp
- Daily irradiation on the panel plane: 5 kWh/m² (i.e., 5 equivalent sun hours at a reference of 1000 W/m²)
- AC energy measured that day: 20 kWh
- Final yield: 20 kWh ÷ 5 kWp = 4 kWh/kWp
- Reference yield: 5 kWh/m² ÷ 1 kW/m² = 5 hours
- PR = 4 ÷ 5 = 0.80, i.e. approximately 80 percent
Measuring irradiance in the plane of the array gives the most accurate result; the standard defines how accurately horizontal and plane-of-array measurements should be made. Since homes do not have pyranometers, satellite or local weather data or the inverter's estimate is usually used. In this case PR is not an absolute "grade" but an indicator used to track the trend of your own system.
For reference, one study reports that PR values have risen over time and generally fall in the 75-90 percent band for installations after 2010. In an assessment for US federal agencies, a PR of 85 percent and an availability of 95 percent are cited as achievable targets. These figures vary by region and system; do not raise an alarm based on a single daily value, look at the weekly and monthly averages.
What to check first when PR drops
In summer, temperature naturally lowers PR; this is not a fault. For a sudden or lasting drop, you can follow this order: inverter error logs, differences between string currents, soiling and shading, outage durations. For a detailed inspection workflow, you can use our article on fault diagnosis when the system produces too little We have also explained the factors that reduce efficiency separately.

How to monitor battery status remotely?
In battery systems, the most critical and most misunderstood part of monitoring is the state-of-charge percentage (SOC). This value is not read from a sensor, it is calculated. In the academic literature, SOC is regarded as one of the core tasks of a BMS, and since it depends on age, ambient temperature and many other factors, its estimation is a complex process. In practice, two methods stand out: coulomb counting, which counts the charge going in and out by integrating current over time, and estimates that make use of voltage. In coulomb counting, sensor errors can accumulate; in field applications it is known that signal noise leads to cumulative errors .
How much drift does a small offset cause?
Assumption: a 48 V (nominal) 200 Ah lithium battery bank, approximately 48 × 200 = 9.6 kWh of nominal energy. The current sensor mistakenly reads 0.5 A too high continuously.
- Error accumulated in 24 hours: 0.5 A × 24 h = 12 Ah
- Its ratio to the bank: 12 ÷ 200 = 6 percent
- If no correction is made, the SOC indicator can actually drift by 15-20 percent within a few days.
For this reason, most systems recalibrate the percentage at the end of a full charge at certain intervals. This behavior usually shows up as the SOC changing suddenly on the day charging completes; it is not a fault. Still, if the change is large, the bank's actual capacity may have dropped. In that case a capacity test is needed; for the methods, see the articles lithium battery capacity test and capacity and health testing in a solar energy battery bank .
Different readings for lead-acid and lithium
- Lead-acid (gel, AGM, OPzV): Voltage is sensitive to load and state of charge; resting voltage gives a rough idea of SOC, but readings under load are misleading. Temperature compensation is critical. Check on the monitoring screen whether the charge voltage is adjusted according to temperature.
- LiFePO4: The voltage curve is very flat over a wide range; therefore it is hard to derive SOC from voltage, and the BMS's coulomb counting becomes decisive. Cell voltage difference, the highest and lowest cell voltage and temperature should also be tracked separately in the monitoring data. The LiFePO4 battery article provides details.
In banks with multiple lithium modules, some systems show only total values. If there is BMS communication that provides cell-level information (for example, a CAN or RS485 line between the inverter and the BMS), check whether you are passing it to the monitoring portal. Balancing problems first appear as cell deviation; for this topic see battery balancing article.

Alarm design: which thresholds, which notifications?
A good monitoring system frees you from constantly watching a screen. The way to achieve that is to define a small number of meaningful alarms. Setting up alarms for everything eventually leads to notifications being ignored.
| Alarm | Possible cause | First step |
|---|---|---|
| Inverter offline | Wi-Fi/network outage, modem failure, inverter shutdown | Check the router and network first; then the status on the inverter's display |
| Zero or very low production during the day | No grid power, protection tripped, DC fuse/switch open | Record the error code; leave any work inside the panel to authorized personnel |
| Production clearly below expected (for example, several days in a row) | Dirt, shading, a string being out of service | Compare string currents and look for the source of shading |
| Low battery state of charge | High consumption, insufficient production, capacity loss | Review the load and charging profile |
| Battery temperature high/low | Insufficient ventilation, overcurrent, cold environment | Check ambient conditions and current level; if heating continues, reduce the load and notify authorized service |
| BMS protection/fault warning | Over/under voltage, cell imbalance, current limit | Manufacturer's manual; do not try to reset it yourself |
| Grid outage and switch to backup mode | Distribution grid failure | Informational notification; if it lasts long, prioritize loads |
When setting thresholds, first review two to three weeks of normal operating data. For example, in a system where daytime production typically exceeds 3 kW between 11:00 and 14:00, anything below 1 kW during those hours could be a reason for an alarm; however, season, tilt angle and shading may call for a different threshold. For the effect of panel layout and shading, see the article on bypass diodes and shading which is useful.
Also consider the notification channel: critical alarms (for example battery temperature, BMS protection) should arrive as instant push notifications or SMS rather than email. Minor daily summaries can be left to a weekly email. In businesses, determine in advance who is responsible for alarms and how they are routed at night and on weekends.
What criteria should you look at when choosing a monitoring system?
Rather than the brand, evaluate the following points according to your needs:
- Compatibility: Does it speak the same protocol as the inverter, charge controller and BMS? Support for an open protocol (for example Modbus) makes it easier to replace devices in the future.
- Data resolution and retention period: How long is minute-level data stored? Is export (CSV, etc.) possible?
- Offline operation: Is data buffered on the device when the internet is down?
- Battery detail: Is it only SOC, or is there also voltage, current, temperature and cell data?
- Alarm flexibility: Can the thresholds and notification channel be set by the user?
- Cybersecurity: Strong password, two-factor authentication, firmware updates; avoid configurations that expose the device directly to the internet.
- Access rights: Can the service team be given temporary and restricted access?
- Continuity: Are the duration of the portal service and any possible subscription terms clear?
It is also important to check the documents and standards of the products; we have gathered this topic in our article on documents and standards .
Additional sensors: when are they needed?
At residential scale, inverter data is usually sufficient. However, additional measurement is useful in the following cases:
- Irradiance sensor: To calculate PR more accurately and to provide a reference in disputes over production guarantees. The standard states that measurement in the plane of the panel improves accuracy in the performance ratio calculation.
- Panel back-surface temperature: For temperature-corrected PR.
- Independent energy meter: To verify the inverter's measurement and to view grid import and load consumption separately.
- Battery temperature sensor: Especially for charge voltage compensation in lead-acid banks.
NREL's operations and maintenance guide emphasizes that data presentation, equipment quality, and the monitoring approach should be addressed separately in monitoring. Calibration of measurement equipment is also important; according to the DOE table, calibration is recommended roughly every 5 years for small systems (under 250 kW). These intervals are general guidelines that do not have to be applied exactly at the household scale.

Interpreting the data: weekly and monthly routine
In NREL's monitoring procedure, who will check the data, how often it will be reviewed, and how it will be reported are determined from the outset; it notes that a weekly review is the minimum, while a daily glance is better, especially in the early period. A practical routine for a home user could be as follows:
| Frequency | Check | Note |
|---|---|---|
| Daily (30 sec) | Is the system online? Are there any notifications? | Not necessary if an alarm is set up |
| Weekly | Production curve, end-of-day battery charge level, error logs | Compare days with similar weather |
| Monthly | Total production, PR or comparison with expected production, grid import/export balance | The manufacturer's or an independent production calculator can be used for the estimate |
| Seasonal | Battery capacity trend, cell voltage difference, effect of panel soiling | Plan a field inspection and tests if necessary |
| Annual | Change in production compared to the first year, software updates, connection and cable inspection | Periodic maintenance with qualified personnel |
PNNL's maintenance guide also recommends keeping the monitoring software up to date when manufacturer updates are released. This is truly important, because updates both fix bugs and close security vulnerabilities. Do not forget that an update may affect the operation of the inverter, and follow the manufacturer's instructions.
Periodic maintenance and monitoring complement each other: monitoring says "something is wrong," and maintenance finds "what it is." For a general plan, you can see the periodic maintenance checklist for solar energy systems and for details on the battery side, battery maintenance and extending battery life article.
Common mistakes and safety notes
- Relying only on the cloud portal: An account, subscription, or service outage can block access to your data. Back up important data periodically.
- Accepting SOC as absolutely accurate: The percentage value is an estimate. A capacity test shows the real capacity.
- Making decisions based on a single day's value: Cloud cover, snow cover, or temperature can make a big difference in a single day; follow the trend.
- Never reviewing alarm thresholds: Thresholds should also be updated as the season and load change.
- Weak passwords and default settings: Devices accessible from outside carry a cybersecurity risk.
- Looking at the data on the screen and intervening in the panel on your own: The DC side carries high current and voltage; there is a risk of arcing and electric shock. Fuse, switch, and cable checks must be performed by authorized electrical personnel. For a detailed framework, see occupational safety in UPS and battery work article.
- Ignoring battery warnings: Temperature rise, a rapidly increasing cell difference, or repeated protection warnings should be taken seriously. We covered the topic of safety in lithium systems in the fire safety article.
You can also link production data to investment evaluation; measured actual production moves the payback period calculation from assumptions to real data.
Monitoring for businesses and critical loads
In businesses, monitoring is not only a tool for saving but a tool for continuity. If solar energy, batteries, and UPS are used together, seeing grid, production, battery, and critical load data on a single panel makes decisions easier during an outage. We explained how critical loads are supplied in the rooftop solar power plant and UPS article; for systems with storage, the solar power plant with storage article will also be useful.
In multi-location businesses, a shared monitoring dashboard makes branch-based comparison possible. If the production of one of two branches of the same size falls behind, the cause is usually a local problem (shading, soiling, a disconnected string). Here too, what matters is having it in writing who will respond to which alarm and within what time. Matters such as regulations, net metering, and metering depend on the current regulations of the distribution company and relevant institutions; for these topics, unlicensed electricity generation and rooftop solar power plants and check the official pages of EPDK (the Energy Market Regulatory Authority), the Ministry of Energy and Natural Resources, and your distribution company for up-to-date information.

Support for batteries, inverters and UPS systems with Bempower
If the monitoring data points to a problem on the battery or inverter side (a battery bank that discharges quickly, a recurring inverter fault, a critical line running together with a UPS), you can use Bempower's survey, installation, periodic maintenance and technical service offerings. Solar panel installation and solar power plant (GES) applications are not covered by these services; we provide on-site support for battery, inverter and UPS systems in Istanbul and the surrounding provinces.
For your request, you can contact us via the contact page and start the process by sharing the devices in your system and the alarms you see.
- IEC 61724-1: Photovoltaic system performance - Part 1: Monitoring — IEC / iTeh Standards catalog, 2017. https://standards.iteh.ai/catalog/standards/iec/6ae4a07c-3eea-4cfe-b563-90ec730e971a/iec-61724-1-2017
- EN IEC 61724-1:2021 Photovoltaic System Performance Monitoring Standard — CENELEC / iTeh Standards catalog, 2021. https://standards.iteh.ai/catalog/standards/clc/f594cb6b-04b9-426a-8505-5cf310be6967/en-61724-1-2017
- Performance Ratio — Sandia National Laboratories PV Performance Modeling Collaborative, 2022. https://pvpmc.sandia.gov/modeling-guide/5-ac-system-output/pv-performance-metrics/performance-ratio/
- Life Cycle of Photovoltaic Systems: Operate and Maintain an Existing Photovoltaic System — U.S. Department of Energy (FEMP), 2026. https://www.energy.gov/cmei/femp/life-cycle-photovoltaic-systems-operate-and-maintain-existing-photovoltaic-system
- Solar Photovoltaic - O&M Best Practices — Pacific Northwest National Laboratory (PNNL), 2023. https://www.pnnl.gov/projects/om-best-practices/solar-photovoltaic
- State of Charge Estimation for Lithium-Ion Batteries Using Model-Based and Data-Driven Methods: A Review — IEEE Access, 2019. https://ieeexplore.ieee.org/document/8843918/
- A parameter adaptive method for state of charge estimation of lithium-ion batteries with an improved extended Kalman filter — Scientific Reports (DOI: 10.1038/s41598-021-84729-1), 2021. https://www.ncbi.nlm.nih.gov/pmc/articles/PMC7952569/
Sources