If Your Solar Energy System Produces Too Little: Fault Diagnosis and Checklist
If your solar energy system produces less than you expected, there may not be a single cause. Sometimes the problem is dirt on the panel surface, sometimes the inverter is limiting its output, and sometimes it is a loose connector in a string or a battery that never fully charges. Because production loss usually grows slowly over weeks or months rather than all at once, it is also hard to notice.
In this article, we will first put "low production" into numbers: how to estimate expected production, what the performance ratio is, and which deviations are normal. Then we will collect the possible causes on the panel, inverter or charge controller, cabling and battery side in a table with symptom, cause and first check columns. At the end you will find a safe step-by-step checklist and criteria for calling a service technician.
The article was prepared for home users, business owners with rooftop or ground-mounted systems, technical managers and purchasing departments. Some of the checks can be done by eye and from the monitoring screen; measurements on the DC side, opening covers and connection work belong to authorized electrical personnel, and we will point this out separately in the relevant sections.
Is your production really low? How do you determine expected production?
The first step is to define the word "low." A system's output naturally varies with the season, cloud cover and panel temperature. Therefore, comparing the monthly kWh value only with the previous month is misleading. A more reliable method is to compare with the same period of previous years or with the actual irradiance reaching the panel surface.
In the industry, the performance ratio (PR) is used for this. PR is the ratio of the measured energy to the reference energy calculated from the installed DC power and the irradiance reaching the panel surface; in the IEC 61724 standard it is defined not as an efficiency but as a ratio normalized to expected production . The monitoring part of the standard describes terminology, measurement equipment, data collection and analysis practices . PR is not an "efficiency percentage"; therefore it should not be confused with panel efficiency, which is 10-20 percent.
A simple calculation example
The numbers below are assumptions chosen only to illustrate the method:
- Installed power: 5 kWp (DC, STC value).
- Irradiance on the panel tilt on the chosen day: 5 kWh/m². Since STC irradiance is 1 kW/m², this means 5 "peak sun hours."
- Reference production: 5 kWp × 5 hours = 25 kWh.
- Assumed PR for a healthy system: approximately 0.80.
- Expected production: 25 × 0.80 = 20 kWh.
- Actual production read on the monitoring screen: 15 kWh.
- Actual PR: 15 / 25 = 0.60.
In this example, 15 kWh is obtained when 20 kWh is expected; that is, production is about 25 percent short, and this cannot be explained by season or clouds. If you do not know the irradiance, comparing two similar sunny days or asking the installing company for the annual production estimate report is the second-best option.
How much deviation is normal?
Not every system performs exactly at its design estimate. In field data from the USA, it has been reported that the median system falls about 5 percent below expectation, while 75 percent of systems perform within 10 percent of expectation . Another NREL study shows that about 9 percent of losses can be recovered with optimal operation and maintenance . As a result, a 5-10 percent deviation alone is not considered a cause for alarm; a deviation above 15-20 percent or one that keeps growing should be investigated.
In addition, some loss items must be taken into account from the start. For example, in PVWatts defaults, items such as soiling, shading, mismatch, wiring, connections and availability add up to a total loss of about 14 percent; the total loss observed in the field fleet was found to be around 8 percent . In other words, a "system loss" of 10-20 percent is already the reason why PR comes out in the 0.80-0.90 range.

First question: What is your system type and where does the symptom appear?
The same symptom has a different meaning depending on the system type. To recall the basic operating logic of the systems, you can see our article explaining how a solar energy system works, and to tell the types apart, see the comparison of on-grid, off-grid and hybrid systems . Here let us summarize only the differences that matter for diagnosis:
- On-grid (grid-connected, no battery): If the grid voltage or frequency goes outside the limits, the inverter stops or reduces production. Production is read from the monitoring screen and the meter.
- Off-grid (with battery, no grid): If the battery is full, the charge controller deliberately limits panel power. In this case low production is not a fault; it means "unused energy."
- Hybrid: The grid, the battery and the load all have an effect at the same time. Production depends on the battery charge level and the load priority setting. For this logic you can look at the hybrid inverter article .
So first find the answer to this question: Is the production loss present all day, only at certain hours, across the whole system or in a single string? These three distinctions narrow down half of the cause.
Panel side: Soiling, shading and temperature
The most frequent and cheapest-to-fix causes of production loss are on the panel surface. For panel types and efficiency factors you can read the article on factors that reduce panel efficiency ; here we cover the diagnostic aspect.
Soiling
Dust, pollen, bird droppings, industrial dust and dry periods without rain block irradiance. The size of the loss varies greatly by region. In Sandia and NREL studies, soiling loss is treated as "variable" depending on the site and cleaning interval; in NREL fleet data this item is reported not as a fixed percentage but as a variable . Rain usually washes off light dust but leaves sticky stains behind. A thin film can form even on a surface that looks clean to the eye. For cleaning method and frequency, see our article on panel cleaning and maintenance . For cleaning that requires climbing onto the roof and walking on wet panels, keep the risk of falling and electric shock in mind; if possible, work from the ground with long-handled systems or with a team that does this job.

Shading and bypass diodes
A newly growing tree, an extension of a neighboring building, an antenna placed on the roof or a chimney shadow can reduce the output of a panel array disproportionately. In series-connected panels, the cell producing the least current limits the current of the string. Bypass diodes inside the panel reduce the loss by bypassing the shaded section; however, partial shading still causes a noticeable loss. For details on the subject, you can look at the article on shading and bypass diodes, and for a panel-level rather than string-level solution, at the article on microinverters and optimizers .
Diagnostic tip: If the production curve is normal at noon but clearly low in the morning or evening, shading is a very strong candidate. Since shade changes with the sun's height over the year, the problem may also appear only in certain months.
Temperature
The power of crystalline silicon panels drops as cell temperature rises. That is why the PR value on a July afternoon may come out lower than on spring days; this is not a fault but a physical effect. The temperature coefficient is given in the manufacturer's datasheet. It is known that temperature changes PR seasonally, and that PR rises in cold and moderate irradiance . Panels mounted very close to the roof with limited ventilation run hotter.
Panel damage: Microcracks, hot spots and aging
Over time, or due to poor handling, hail or incorrect stepping, cell cracks can form inside the panel. The IEA PVPS Task 13 report states that in addition to the risk of power loss, cell cracks also carry the risk of hot spots and burn marks due to inactive cell sections . A hot spot is when one cell heats up more than the others; it is easily seen with a thermal camera and is important in the long term for panel and fire safety.
Normal aging, on the other hand, is slow. In field studies the average annual power loss mostly ranges between 0.5 and 1 percent; NREL's field fleet study counts faster degradation than 0.5 percent/year and unnoticed partial outages among the performance loss factors . A rapid decline cannot be explained by aging. The signs below may indicate panel damage:
- Cracks in the panel glass, brown or burnt spots on a cell, bulging or discoloration on the back surface.
- The voltage or current of one panel being clearly different from neighboring panels (measurements must be taken by authorized personnel).
- A cell or panel showing up distinctly hotter than its surroundings on a thermal camera.
- A drop in output that begins after hail, a storm, snow load, or a heavy object falling.
If you suspect damage, do not climb onto the panel and do not disconnect the cable; a panel always produces voltage in daylight, and remember that the DC string voltage is high.
Inverter and charge controller: Temperature, curtailment, and error codes
The inverter converts the direct current from the panels into usable alternating current; in battery systems this job is shared between the charge controller and the inverter. A significant share of production problems originates here. DOE FEMP states that capacitors and printed circuit boards are common sources of inverter problems .
Error code and alarm history
The inverter display or app log is the first clue to a fault. Grid overvoltage, insulation (isolation) faults, DC overvoltage, overtemperature, and fan warnings are the most common. Because error codes vary by brand and model, read the meaning of the code in the user manual. For hybrid devices, in our article hybrid inverter faults and error codes we covered battery, panel, and grid warnings separately. Note down the codes; when you call for service, the date and time of the code is the most valuable information. In its maintenance guide, DOE also recommends an electrical inspection after the inverter repeatedly trips on and off as a "nuisance" .

Power derating due to temperature
If the inverter overheats, it reduces its output power to protect itself. Causes include a fan clogged with dust, a unit installed inside a closed cabinet, or a wall that receives direct sunlight. The symptom is a flattened and "jagged" production curve in summer afternoons. The solution usually lies in placement, ventilation, and maintenance.
Grid-related curtailment
When the grid voltage is high (especially around midday in neighborhoods with many solar plants), the inverter reduces its power or disconnects according to its safety settings. This is not a fault in your system; however, measurement and resolution require working with the authorized service and the distribution company. Do not change grid settings yourself.
Sizing and clipping
If the panel power is much higher than the inverter power, the inverter clips the excess at summer noon. This may be a design choice; however, effects such as a high DC/AC ratio and clipping can mask performance problems . In other words, a problem can stay hidden while the PR looks good. To understand the real loss, look both at the shape of the curve and at whether the inverter output stays at a fixed ceiling.
MPPT window and string compatibility
MPPT is the tracking algorithm that keeps the panel string operating at its maximum power point at all times. If the string voltage falls outside the MPPT range of the inverter or charge controller (voltage drops in hot weather and rises in cold weather), the device operates inefficiently or not at all. If the number of panels in the string is wrong, or a panel has failed and dropped out, the string voltage will also differ. You can find the difference between MPPT and PWM in our related comparison article, and panel string and device compatibility in our article on choosing a charge controller .
Cables, connectors, and protection devices: Silent loss points
Wiring problems not only reduce production but also create a safety risk through heating and arcing. Common problems include:
- Loose or poorly tightened connection: Resistance increases and the connection heats up; in the long term it creates a risk of burning and arcing.
- Connector pairs from different brands or incorrectly crimped terminals: Contact resistance rises.
- Insufficient cable cross-section: Voltage drop grows, especially in low-voltage (12 V, 24 V) battery systems. For the calculation method, see the DC cable cross-section article .
- Blown or weakened DC fuse and switch: The string drops out and production may fall by half. How to select protection is explained in the article on DC fuses, switches, and surge arresters .
- Damage after lightning or a grid surge: The surge arrester may have done its job and need replacing; for grounding, take a look at the article on grounding and lightning protection .
- Rodent, UV, and moisture damage: Cable insulation may be damaged and a ground leakage may have occurred; the inverter will also trip by reporting an insulation fault.
All of these parts are under DC voltage and cannot be switched off while there is light. Tasks such as disconnecting a connector, removing a fuse, or tightening a connection must be performed only by authorized and properly equipped personnel. Unlike an AC arc, a DC arc does not extinguish on its own and can cause serious injury or fire. What you can do is look visually, note signs such as discoloration, melting, a burning smell, or crackling, and report the system to the service representative if any of these signs are present.

The appearance of "low production" in battery systems: Battery, charge settings, and load
In a battery system, a low value on the production display is not always a panel problem. If the battery is full, loads are low, and the charge controller is throttling panel power, production is deliberately low. Conversely, if the battery is always empty, the problem is not in production but in the balance between consumption and capacity. On the battery side, distinguish between the following situations:
- The battery fills up during the day and production is throttled: This is normal operation. The system size may be appropriate; shifting loads to daytime can be considered.
- The battery never fills up: Panel power may be too small relative to daily consumption. For sizing, the article on how many panels are needed and the battery capacity calculation will help.
- Charge voltage settings are wrong: Bulk, absorption, and float values that do not suit the battery type either do not fully charge the battery or wear it out unnecessarily. For details, see our article on charge settings; these settings should be made by the authorized service according to the battery manufacturer's values.
- Battery capacity has dropped: In an aged lead-acid battery, sulfation or cell imbalance may be the cause; run a capacity and health test in the battery bank testing article .
- BMS limit on a lithium battery: Because of cell temperature or imbalance, the battery management system may limit the charging current. The logic behind this is in the BMS article explained.
If there is swelling, electrolyte leakage, overheating, or an alarm on a lithium module in the battery bank, do not touch the unit; ventilate the area and notify authorized service. Lead-acid battery compartments can release gas; for fire safety in lithium storage, see our lithium battery fire safety article for more information. Since this section concerns a battery problem, the Bempower service team can help if you want technical support for UPS and battery systems.

Symptom, likely cause, and first check: Fault diagnosis table
The table below matches common symptoms with likely causes. The "First check" column lists observation steps that can be performed safely on the user side; work that requires measurement should be left to authorized personnel.
| Symptom | Likely cause | First check | Who should do it? |
|---|---|---|---|
| Low all day, curve normal in shape | Widespread soiling, cloud cover, seasonal effect, panel aging | Compare with previous days under similar conditions; inspect the surface | User |
| Low in the morning or evening, normal at noon | Partial shading (tree, chimney, antenna) | Observe how the shadow moves through the hours | User |
| Curve flattens in the afternoon | Inverter overheating derating, clipping, high grid voltage | Device temperature, fan noise, ventilation, alarm history | User observation, service measurement |
| One string very low or zero | Blown fuse, loose connector, faulty panel, cable damage | Compare production data string by string | Authorized electrical personnel |
| Sudden drop, error code present | Insulation fault, DC overvoltage, grid fault, board failure | Record the code, its time, and how often it recurs | Service |
| Battery not charging, production high | Excessive load, wrong charge setting, low battery capacity | Battery voltage, charge current, day-night consumption log | User observation, service test |
| Battery full, production appears low | Charge controller is deliberately limiting power | Battery charge percentage and load during the day | User |
| Discoloration or odor at the connector | Loose or damaged connection, high contact resistance | Visual inspection without touching; report the system to authorized personnel | Authorized electrical personnel |
| Low or off after a lightning strike | Surge arrester, inverter input, or board damage | Alarm and protection indicators | Service |
| Slow decline over the years | Aging, permanent soiling, micro-cracks | Compare annual production, thermal camera | Service |
Evaluate the symptoms together, not individually. For example, if high temperature, low noon production, and a fan warning occur together, inverter overheating stands out; if a drop in a single string comes with a discolored connector, a connection problem is likely.
Step-by-step safe checklist
The order of checks matters: first monitoring data, then visual inspection, and measurement last. The list below shows the division of tasks between the user and authorized service. For a regular maintenance schedule, you can also review the periodic maintenance checklist .
1. What can be done on the user side
- Collect the data: Transfer the daily production for the last 30 days, the weather, and the inverter's alarm history into a table. The DOE also recommends regularly checking energy production meters and the error messages on the inverter display .
- Examine the daily curve: We look for a low morning and evening output, a flattened midday peak, a sudden dip, or a flat zero line.
- Inspect the surface from ground level: Dust, bird droppings, leaves, a new source of shade, cracked glass. Is there a new antenna, air conditioning unit, or tree shading the panels?
- Check the area around the inverter: Is the unit covered, are the vents blocked, is the fan noise abnormal, is there a temperature alarm?
- Look at the protection device indicators: Information that can be read from the outside, such as the top of the breaker cover or the surge arrester indicator, without opening any cover.
- Record the battery readings: End-of-day charge level, overnight consumption, and charging current; has a new device been added to the load list?
- Restart: Only if it is described in the manual and the fault is not persisting, and only once. If the fault recurs, do not repeat it.
2. What the authorized service will do
- String voltage and current measurement: Compare the open-circuit voltage and operating current with the expected values for each panel and string.
- Insulation and earthing measurement: Check whether there is any leakage.
- Thermal camera scan: Hot spots, heated connectors, or fuse holders.
- Connection tightness and connector check: Verify the torque against the manufacturer's value.
- Inverter and charge controller settings: Grid parameters, MPPT range, battery type and charging voltages, firmware version.
- Battery capacity and internal resistance/conductance test: Verifying battery health in battery-backed systems.
- Report: Findings, measurement values, and recommendations should be provided in writing.
For performance checks, the DOE operations and maintenance guide cites as a criterion whether the system is operating within 80 percent of its weather-corrected performance ratio. This is not a definitive threshold for every system; use the target in your design report as the basis.

Common mistakes and things you should not do
- Looking at only one day of data: Mistaking a cloudy day for a fault is the most common error; evaluate at least several days together with irradiance.
- Mistaking low production for a fault when the battery is full: The charge controller may be limiting power.
- Cleaning by walking on the panels or with a hard brush: Microcracks and surface scratches create new losses; follow the manufacturer's instructions.
- Disconnecting the DC connector under load: An arc may form and cause serious injury; this task is for authorized personnel only.
- Changing settings by trial and error: Entering the wrong grid, charging voltage, or MPPT settings puts both the warranty and the battery at risk.
- Clearing the error code without taking notes: The alarm history is valuable data for the service technician.
- Not monitoring at all: In rooftop systems, noticing a fault and dispatching a technician often takes a long time, due to inadequate monitoring and labor costs. That is why even the simple remote monitoring described in our monitoring systems article provides early warning.
Winter, aging, and "normal" losses: avoiding false alarms
Not every drop is a fault. The drop in winter production is caused by shorter days, a low sun angle, and cloud cover; for planning around this, see the winter production article Panel tilt and orientation also determine the production distribution throughout the year; for this, see the panel tilt and orientation article will help.
Expectations should also be realistic. A panel's rated power is based on laboratory (STC) conditions; on the roof, temperature, angle, cable losses, and inverter efficiency reduce it. If you are calculating payback based on a production estimate, check whether the assumptions in the payback period article include these losses.
In grid-connected rooftop solar plants, the value reflected on your bill depends not only on production but also on consumption and the netting arrangement. However, even if production falls short, the regulations and tariff information on this subject change over time; for the current situation, see the official pages of EPDK, the Ministry of Energy and Natural Resources, and your distribution company.
When should you call a professional service?
In the following cases, stop your own checks and notify the authorized service:
- If the same error code repeats for several days in a row.
- If a string or group of panels is not producing at all.
- If there is a burning smell, discoloration, melting, crackling, or excessive heat around a connector, cable, inverter, or battery.
- If the circuit breaker or fuse trips frequently.
- If production has dropped after lightning, flooding, a storm, or hail.
- If there is battery swelling, leakage, a BMS alarm, or high temperature.
- If production loss exceeds 15-20% and cannot be explained.
Having the following information ready when you request service speeds up the process: the installation date and type of the system, the panel and inverter model, error codes and when they occurred, recent production data, and photos. For panel-side installation or project matters, you should consult your installation company or authorized electrical engineers. Bempower does not provide solar panel installation or solar power plant (GES) application services; however, it does support inspection and service requests for UPS, battery, and inverter equipment.
If the system includes a UPS, battery bank, or inverter and the problem is suspected to originate from these devices, you can use Bempower's survey, installation, periodic maintenance, and technical service offerings. With details such as the device brand and model, error codes, and when the problem started, through our contact page get in touch with us, and let us schedule an on-site inspection in Istanbul and the surrounding provinces.
- Understanding Solar Photovoltaic System Performance — U.S. Department of Energy (FEMP), 2022. https://www.energy.gov/sites/default/files/2022-02/understanding-solar-photo-voltaic-system-performance.pdf
- Optimizing Solar Photovoltaic Performance for Longevity — U.S. Department of Energy (FEMP), 2026. https://www.energy.gov/cmei/femp/optimizing-solar-photovoltaic-performance-longevity
- Life Cycle of Photovoltaic Systems: Operate and Maintain an Existing Photovoltaic System — U.S. Department of Energy (FEMP), 2026. https://www.energy.gov/cmei/femp/life-cycle-photovoltaic-systems-operate-and-maintain-existing-photovoltaic-system
- Solar Photovoltaic - O&M Best Practices — PNNL, 2022. https://www.pnnl.gov/projects/om-best-practices/solar-photovoltaic
- Performance Ratio — Sandia National Laboratories PV Performance Modeling Collaborative, 2022. https://pvpmc.sandia.gov/modeling-guide/5-ac-system-output/pv-performance-metrics/performance-ratio/
- EN IEC 61724-1:2021 Photovoltaic system performance - Part 1: Monitoring — IEC / CENELEC (iTeh Standards catalog page), 2021. https://standards.iteh.ai/catalog/standards/clc/f594cb6b-04b9-426a-8505-5cf310be6967/en-61724-1-2017
Sources