What is Battery Internal Resistance? Why is it Important?
In the maintenance report, you'll see a voltage value and a small number in milliohms (mΩ) next to each battery. That number represents the battery's it is the internal resistance and it often indicates that the battery is running low long before the voltage drops. When should a UPS battery be replaced? We briefly touched on this measurement in our previous article; in this article, we explain in detail what internal resistance is, why it increases, and how to interpret the measurement results.
What Is Battery Internal Resistance?
When a battery delivers current, it also encounters internal resistance: the plates, grids, electrolyte, and internal connections create a slight resistance to the flow of current. The total of this resistance internal resistance ... is called. The value is very small; in the 12-volt batteries commonly used in UPS systems, it ranges roughly from a few milliohms to a few tens of milliohms, depending on the size, and decreases as the capacity increases.
You may come across three closely related concepts in measuring instruments:
| Concept | How is it measured? | As the battery weakens |
|---|---|---|
| Internal resistance | A short load is applied to the battery, and the resistance is calculated from the drop in voltage (mΩ) | Increase |
| Impedance | A small AC current is applied to the battery, and the resulting AC voltage is calculated; it includes a small reactive component in addition to the resistance (mΩ) | Increase |
| Conductivity | It shows how easily current flows through a battery; it can be thought of as the inverse of resistance (siemens) | Decreases |
These three measurements together ohmic measurements ...is called. The readings from different methods cannot be directly converted into one another; what matters is measuring the same battery using the same method each time and, if possible, with the same device.
Why Does Internal Resistance Increase Over Time?
In sealed (VRLA) batteries used in UPS systems, aging increases internal resistance in several ways:
- Grating corrosion: The lead grid on the positive plate wears down over time, and the path through which the current flows narrows. High temperatures accelerate this process.
- Electrolyte drying: You cannot add water to a sealed battery. Water lost due to high temperatures or incorrect charging voltage cannot be replenished, and the active surface area decreases.
- Sulfation: When a battery remains undercharged for an extended period, hard lead sulfate crystals accumulate on its plates, making it difficult for current to flow.
These processes occur silently. The battery continues to display normal voltage while idle; the problem only becomes apparent when a high current is drawn. Factors that shorten its lifespan Factors Affecting Battery Life We also addressed this in our article.
What Happens When Internal Resistance Rises?
During a power outage, the UPS draws a high current from the batteries. The higher the internal resistance, the greater the voltage drop and heat generation within the battery at the same current:
- As soon as the power outage begins, the battery voltage drops sharply.
- The UPS reaches the low-voltage threshold sooner than expected, and the runtime is reduced.
- Under heavy loads, the UPS may shut down within the first few seconds of a power outage.
- A single high-resistance battery in a series-connected array heats up and shortens the runtime of the entire group.
How Is Internal Resistance Measured?
Measurements are taken individually from the terminals of each battery using battery testers that operate via the AC impedance, conductivity, or DC load methods. Since the device applies only a very brief and small signal to the battery, the measurement can usually be performed while the UPS is running, without requiring a power outage. However, since battery banks carry high DC voltages, this task should only be qualified technical staff must be performed by [name], wearing appropriate protective equipment.
To ensure that the measurements are comparable, the conditions are kept the same each time:
- Always connect the probe to the battery terminal—not to the connection cable or the bolt.
- The battery is fully charged and in float charge mode; it is not measured immediately after a discharge.
- The battery temperature is also recorded; a cold battery has a higher internal resistance.
- The connection resistance between the batteries is also measured. A loose or corroded connection may appear to be a battery failure; the solution is not to replace the battery, but to clean the connection and tighten it properly.
How Should the Results Be Interpreted?
A single measurement alone tells us very little. Since values vary depending on the battery type, capacity, and manufacturer, there is no general threshold where we can say, “Anything above this number is bad.” What is meaningful are two comparisons:
- Changes over time: When the battery is new, the readings taken during the first few months after installation baseline value It is compared with subsequent measurements. The rate of increase tells us more than the value itself.
- Other batteries in the series: Batteries of the same group and age should have similar readings. Any battery that deviates significantly from the average is examined separately.
Guidelines developed for stationary batteries, such as IEEE 1188, recommend recording the initial value and conducting a further inspection of the battery when a significant increase from that value is observed. In common field practice, an increase of roughly 20–30 percent above the initial value is considered a trigger for inspection, while an increase of 50 percent or more is regarded as a sign of serious deterioration. These percentages are merely a guideline; The values provided by the battery manufacturer are the standard. If there is no initial value, the first measurement is recorded as a reference, and the evaluation is based on a comparison of the batteries in the array.
Can an Internal Resistance Measurement Replace a Discharge Test?
No. Internal resistance measurement is a fast, continuous, and powerful monitoring tool that can be performed on an individual battery; it provides early warning of a failing battery. However, the actual number of minutes a battery bank will last during a power outage can only be determined in a controlled capacity (discharge) test shows. The two complement each other: regular measurements indicate which battery needs to be tested and when, while the discharge test confirms that decision. How to perform the test How to Perform a Battery Discharge Test We explained this in our article.
How Is Internal Resistance Displayed in the Maintenance Report?
During routine maintenance, batteries are tested individually, not as a group. The report typically includes the following information for each battery:
| Column | What does it mean? |
|---|---|
| Battery No. | The battery's location in the array; the same battery is tracked by the same number during every maintenance check |
| Voltage (V) | Charge status and balance among the batteries |
| Internal resistance (mΩ) | Battery Ageing Status |
| Temperature (°C) | Test conditions and overheating batteries |
| Conclusion | Well, it should be monitored or changed |
At each visit, the values are compared with the previous measurement; batteries that deviate from the others or show rapid changes are specifically noted in the report. Other checks performed during maintenance What is UPS maintenance? In this article, we discuss the visit frequency options Maintenance Plans You can find it on our page.
- IEEE Std 1188-2005 — Recommended Practice for the Maintenance, Testing, and Replacement of Valve-Regulated Lead-Acid (VRLA) Batteries for Stationary Applications
- Product manuals and data sheets from UPS and battery manufacturers (specifications vary by manufacturer)
Sources
How to Interpret Internal Resistance Measurement?
Internal resistance measurement is not assessed by looking at a single number, but through a four-step process.
What is decisive is the change of the same battery over time and the difference with other batteries in the series. The decision is based on the values of the battery manufacturer and, if necessary, verified by a discharge test.
Frequently Asked Questions
01Is it necessary to turn off the UPS for internal resistance measurement?
02Can a battery with normal voltage have high internal resistance?
03How often should internal resistance be measured?
04Is there any point in measuring the internal resistance of new batteries?
05Should a battery with high internal resistance be replaced immediately?
Let's Measure the Internal Resistance of Your Batteries
During periodic maintenance, we measure the voltage, internal resistance and temperature of each battery one by one, and report the results by comparing them with previous visits. For details Periodic Battery and UPS Maintenance page, for situations where change is required Battery Replacement and Reconditioning page. Your UPS brand and model, the number of batteries and the last measurement results, if any. Send us; Let's evaluate the condition of your batteries together.