TCMB foreign exchange selling rate · 25.11.2026: USD 50,64 ₺ EUR 55,40 ₺

What is Battery Balancing? Voltage Equalization in Series Battery Groups

What is Battery Balancing? Voltage Equalization in Series Battery Groups

The battery of a UPS or energy storage system looks like a single "box", but often consists of dozens of elements connected in series. A 48 V UPS array is built with four 12 V blocks, and a series of 192 V is built with sixteen blocks. In a series connection, the same current flows through each element, but not every element holds the same voltage and the same charge level. This difference starts out small, but can grow over time. Eventually, the group reserves much less time than it should.

In this article, we discuss what battery balancing is, why voltage is distributed in series groups, and how balancing is done differently in lead-acid and lithium systems. You will also find passive and active balancing methods, the logic of equalization charging, calculation examples and common mistakes. Article; It is prepared for UPS and battery responsible technical personnel, facility managers, purchasing units and home or business owners who are considering switching to lithium storage.

Important note: Battery strings carry high DC voltage and can deliver very high current in the event of a short circuit. The information in this article is to make it easier for you to make a decision. Operations such as connection, adjustment and change of charging voltage must be carried out by authorized electrical personnel or technical service.

What is Battery Balancing?

Battery balancing; It is the process of bringing the state of charge (SoC, that is, the charge rate) and voltage of batteries or cells connected in series closer to each other. The aim is to prevent any element from being overcharged or discharged prematurely. The term is also referred to as "cell balancing", "charge equalization" in the literature and "cell equalization" or "voltage equalization" in Turkish.

The concept is applied slightly differently in two worlds:

  • Lead-acid (VRLA, AGM, gel, OPzS/OPzV): The elements are usually 2 V cells or 6/12 V blocks. Balancing is mostly achieved by the correct setting of the charger, temperature balance, measurement and, if necessary, equalization charging.
  • Lithium (LiFePO4, NMC, etc.): Each cell or parallel cell group is monitored by the BMS (Battery Management System). The balancing circuit is on the BMS board and works automatically.

In short, balancing is not a "luxury", but a basic process required for the healthy operation of a serial array. The usable capacity of the array is often determined by the weakest element.

Battery rack view showing voltage difference in VRLA battery blocks connected in series

Why is the voltage not evenly distributed in series battery groups?

The same current flows through the elements connected in series; however, the state of charge is not equalized by "the current being the same". Because the charge rate is determined by the capacity of each element. Even two similar batteries decompose over time for several reasons:

  • Manufacturing tolerances: The amount of active substance, plate quality and electrolyte amount are not exactly the same.
  • Difference in self-ejaculation: If one element is ejaculating a little faster than the other, the difference accumulates day by day.
  • Temperature Difference: The battery on the upper floor of the shelf does not charge in the same way as the one on the lower floor; the heated battery behaves differently. The effect of temperature is also Factors Affecting Battery Life You can find it in the article.
  • Internal resistance difference: Aging, sulfation or drying increase the internal resistance of an element; this element sits at different voltage value at charge. For details Battery internal resistance You can check our article.
  • Connection Quality: A loose or oxidized terminal creates additional resistance and voltage drop (Unbalanced voltage and terminal corrosion in the battery bank).

In float charging, the charger applies a single total voltage to the entire string. This voltage is shared between the elements; even if the total voltage is correct, some elements may remain at higher voltage than others and some at low voltage. A VRLA technical paper for telecom supply explains this situation as follows: String voltage is the average of individual elements; therefore, some cells are undercharged, some are overcharged, and capacities move away from each other over time. Manufacturer manuals also cite uneven voltage distribution between cells as one of the main causes of VRLA failures.

Another important point is that the imbalance can feed itself. To remember the battery charge/discharge logic How Battery Charging and Discharging Works You can take a look at the article. The element that remains undercharged approaches sulfation, and the element that remains overcharged makes gas and loses water. Both weaken that element, and the weakened element enlarges the difference.

Consequences of Imbalance: Capacity, Lifespan, and Security

A serial array operates according to the "weakest link" rule. During discharge, the element with the lowest capacity finishes first; even if energy remains in the rest of the string, the total voltage can drop to the UPS's end-of-discharge threshold and the system shuts down. In charging, the element with the smallest capacity or highest resistance fills up early; the charger may reach its voltage limit before the others can be fully charged.

In practice, the following results are encountered:

  • Shorter than expected autonomy period (see Table 1). UPS autonomy time test).
  • Gas release, drying, swelling and temperature increase in high-stress blocks (see Table of Materials). Battery swelling).
  • Sulfation and permanent capacity loss in low-stress blocks (see Table of Materials). Battery sulfation).
  • In lithium, the BMS cuts off charging or discharging because the cell voltage reaches the upper or lower protection limit early. This reflects to the user as "the battery looks full but gives little energy".
  • Uncontrolled overcharging in lithium chemistry increases the risk of thermal runaway. For this risk Thermal runaway You can look at the article.

Voltage equalization in lead-acid battery groups

Float voltage and voltage differential monitoring

VRLA batteries used in UPSs mostly sit in the float, i.e. constant voltage with continuous low current. Manufacturers specify one float voltage per cell and ask you to correct this value for temperature. For example, a manufacturer's manual gives a value of about 2.27 V per cell at 25 °C and says that the setting should be corrected as the temperature changes. Typical values vary by product; the battery data sheet should be consulted for the exact voltage.

The way to monitor the health of the string in the float is to measure tension on a block-by-block basis. For the measurement method How to measure battery voltage and how to interpret it for general charging logic Float voltage and end of discharge You can read the article. In the manufacturers' manuals, block voltages are expected to remain within a certain band around the nominal value. Blocks that are out of the band or move away over time are considered signs for equalization charge or more detailed testing.

What is equalizing charge?

Equalization charging is a controlled and limited-time charge that is specially applied to eliminate the voltage inequality in the string that remains in the float for a long time. The logic is as follows: The string is charged with a slightly higher constant voltage. High-voltage (full) elements do not draw much current, while the lagging elements approach full charge.

Manufacturers usually give the following framework for this process (values vary depending on the product):

  • A VRLA manual considers equalization charging necessary in situations where operation in a float for extended periods of time creates a voltage unbalance. The same manual describes voltage in the range of approximately 2.42-2.45 V per cell at 25 °C at most, and periodic application (quarterly or over a certain number of discharge cycles).
  • Another manufacturer's manual links the equalization charge to conditions such as a certain cell voltage falling below the lower limit or float voltages going outside the specified band, and instructs that the operation be performed with constant voltage.

Do not apply these figures directly to your own system. Equalization voltage, duration, current limit and temperature conditions vary depending on the brand, model and battery type. Improperly applied equalization charging can dry out the battery, heat it up and damage the loads connected to the charger. This should be done by an authorised service centre, paying attention to the settings of the charger and the protection of the loads.

Technician gloved hands measuring voltage with digital multimeter at battery pole

Calculation example: Block voltages in a 48 V UPS array

Assumptions: Four 12 V VRLA blocks connected in series (24 cells total), float voltage 2.27 V per cell, ambient approx. 25 °C.

  1. Total float voltage: 24 × 2.27 V ≈ 54.5 V.
  2. If the blocks were equal, each would be: 54.5 ÷ 4 ≈ 13.6 V.
  3. Measured values: 13.9 V, 13.8 V, 13.5 V, 13.3 V. The total is again around 54.5 V, so the charger appears to be set correctly.
  4. Deviation from the mean: +0.3 V, +0.2 V, −0.1 V, −0.3 V (approx.).
  5. Counterparts per cell: 13.9 V ÷ 6 ≈ 2.32 V and 13.3 V ÷ 6 ≈ 2.22 V.

Comment: Since the total voltage is correct, the panel can say "everything is normal". However, the highest block is significantly above the float value per cell and below the lowest block. The former is heading towards drying and corrosion, the latter towards undercharging and sulfation. This example illustrates why it is misleading to look only at the total voltage. In this type of array, the blocks require equalization charge, followed by a controlled capacity or state test.

When the equalization charge is not enough

Equalization charging recovers the missing charge, but it does not make an aged or damaged block "new". In the following cases, the problem is not the charge balance, but the battery:

  • After equalization, the same block remains at low or high voltage.
  • The internal resistance of the block is significantly higher than the others (for internal resistance measurement internal resistance and conductivity test).
  • There is swelling, leakage, odor or temperature in the block.
  • Group age is close to the end of producer life.

In such cases, the question of whether to replace a single battery or the entire group comes to the fore; criteria Should a single battery or the whole group be replaced? You can find it in the article.

Cell Balancing with BMS in Lithium Batteries

Balancing in lithium packs is one of the main tasks of the BMS. The BMS measures the voltage of each cell (or parallel group of cells); it balances when a cell is ahead of the others, and limits the charge or discharge when extreme voltages are approached. For other tasks of the BMS What is a BMS and what does it do in lithium batteries You can look at the article.

Two distinctions are important here:

  • Parallel cells are self-balanced: The voltage of the cells connected directly to each other equalizes. The main problem arises when parallel groups are connected in series; the BMS balances between these groups.
  • Voltage difference is not the same as capacity difference: Balancing compensates for the difference in charge level, it does not eliminate the aging problem of the cell itself, such as its own capacity. The two situations are different variables and the results are also different.

In LiFePO4 cells, the voltage curve is very flat over a wide occupancy range. For this reason, the charge difference between the cells cannot be read clearly from the voltage; balancing is mostly effective in the upper region of the charge, where the voltage rises. For chemistry differences LiFePO4 vs. NMC You can look at the article.

BMS board and cells connected in series that monitor cells in lithium battery pack

How does passive balancing work?

In passive balancing, the excess energy of the cell that takes the lead in charging is converted into heat through a resistor. Thus, it gives time to other cells to catch up. The circuit is simple and inexpensive; this is why it is found in most commercial BMS. The disadvantage is the low balance current (several tens of mA levels) and the dissipation of energy as heat.

In a DergiPark article, the passive balancing method, in which energy is expended by high-power resistors when the difference between cells exceeds the specified threshold, is described with experimental results. The same study shows that the threshold value determines when balancing begins and ends.

How does active balancing work?

In active balancing, energy is not consumed, it is transported between cells. Energy is transferred from a high-charge cell to a low-charge cell by capacitor, inductance or transformer/DC-DC converter-based circuits. In the literature, these methods are divided into subclasses; A review in DergiPark also compares passive and active systems in terms of battery life. Another DergiPark study examines a buck-boost converter-based active balancing system by analogy.

Active balancing can be faster and more efficient, but the circuit is more complex, more costly, and the circuit's own losses and heating must also be taken into account.

Passive and active balance comparison

FeaturePassive balanceActive balance
The fate of energyTurns into heat in resistanceIt is transported between cells, there is a loss of transformation
Typical balance currentLow (from tens of mA to hundreds of mA)Usually higher (from hundreds of mA to several A, depending on the product)
Circuit complexity and costSimple, lowComplex, higher
Warm-upResistance heating should be consideredConverter losses should be taken into account
Proper useSmall/medium capacity, continuous grid-connected standby systemsLarge capacity, frequent cycles, systems where imbalance grows fast
Point to noteOpportunity (time) is limited; it is mostly effective in the upper region of the chargeThe actual gain depends on the balance current and algorithm in the product's datasheet

Calculation example: balancing current and balancing time

Assumptions: 16-cell (16S) LiFePO4 package, cell capacity 100 Ah, there is a charge difference of 2 Ah between the cells. Losses are omitted.

  1. If the passive balance current is 50 mA (0.05 A), the duration = 2 Ah ÷ 0.05 A = 40 hours.
  2. If the active balance current is 1 A, the duration = 2 Ah ÷ 1 A = 2 hours.
  3. The heat power of passive balance in a single cell is about 3.4 V × 0.05 A ≈ 0.17 W; that is, the heat problem is small, but the balance is very slow.

Comment: If the pack reaches full charge every day and stays at the top voltage for a long time, passive balancing may be sufficient. However, in a system that operates at partial charge for days, the window in which the passive balance will work is too short and the difference may accumulate. Therefore, active balance is evaluated in large capacity or frequently cycled packages. A BMS technical article also states that the power required for balancing is generally low, ranging from 0.1 W to 10 W per cell, and the choice should be made according to the application. For a definitive result, the balancing current and starting threshold in the product's data sheet should be used.

Close-up of electronic board showing passive and active balance circuit concept

Comparison of Balancing Approach in Lead-Acid and Lithium

SubjectLead-acid (VRLA, OPzV, etc.)Lithium (LiFePO4, NMC)
Where is balancing done?With charger and periodic equalization charging; cell-by-cell circuitry usually absentInside the package, on the BMS board, on a cell basis
MonitoringBlock/cell voltage measurement; manually or with a monitoring system during maintenanceBMS continuously reads cell voltage
The impact of overchargingGassing, drying, grid corrosionCell overvoltage; safety risk, cut-off with BMS protection
The impact of incomplete chargingSulfation, permanent loss of capacityReduced usable capacity, premature cutting of BMS
User interventionIf measurement, equalization charging is required, authorized technical serviceNormally none; service in unusual imbalance
Relevant product classesGeneral-purpose, high-current, deep-cycle, and telecom batteriesLithium UPS batteries, home and business storage packs

On the lead-acid side, the choice of battery grade also affects the balance. For which battery to use in which application Which battery is used in which system, for long-lasting industrial options OPzS and OPzV battery You can look at the articles. There are maintenance items different from lead-acid in lithium systems. lithium battery capacity test summarizes.

Parallel Arrays, Old-New Battery and Mixed Use Errors

Imbalance occurs not only in a single serial sequence, but also where sequences converge:

  • Current sharing in parallel arrays: When two or more series strings are connected in parallel, the current is not shared equally if the cable lengths and connection resistances are not equal. A manufacturer's manual recommends that the cables be equal for proper load sharing and the same float voltage in each string. For wiring and busbar arrangement Battery array, series and parallel battery connection can be looked at.
  • Mixing old and new battery: The difference in capacity and internal resistance can leave the new battery overcharged and the old one undercharged.
  • Using batteries of different brands, models or production dates in the same series: Charging and self-discharging characteristics may differ. For compatibility checks Is every battery installed in every UPS? See the article.
  • Uncontrolled commissioning of batteries that have been sitting in storage for a long time: Standby batteries may be self-discharged at different rates; initial charge and voltage check required (Shelf life of the battery).
  • Not checking after a single battery replacement: After replacement, block voltages and charging behavior should be monitored (Commissioning tests after battery replacement).

There is also a different type of imbalance: external "battery balancer" products used in 24 V systems consisting of two 12 V fluxes or in parallel string systems. These step in when the voltage difference between two strings connected in series exceeds a certain level and draw current from the high-voltage string, reducing the difference. It can be useful in small systems with several blocks connected in series; however, a UPS string needs to be considered in conjunction with its charger, setting, and metering, because the balancer will not recover a poorly tuned charge.

Ways to Recognize Imbalance: Symptom, Cause, Solution

SymptomPossible causeWhat should be done?
UPS gives backup too soon as expectedOne or several weak blocks; incomplete chargeBlock-by-block voltage measurement, followed by capacity/condition testing (Capacity and Condition Test Difference)
One block in the float is significantly higher than the othersHigh internal resistance, no drying, no temperature differenceBlock temperature and internal resistance control; comparison with manufacturer's limits
One block is at continuous low voltageTendency to undercharge, sulfation, internal short circuitService evaluation; equalization charging and testing if necessary
White/green deposit at the pole, warmingCorrosion, loose connectionCleaning and torque control by authorized personnel; thermal imager (Control with thermal camera)
BMS cuts off premature charge/discharge in lithiumCell imbalance, small capacity cell, low balance currentChecking cell voltages in the firmware/display; calling for service
Cell voltage difference in lithium increases over timeCell aging difference, insufficient balancing opportunityReviewing charging strategy, consulting with the manufacturer, active balancing if necessary

To read the test results correctly How to interpret battery test results and for regular maintenance plan How to maintain a UPS battery We recommend the article.

UPS battery cabinet with charger panel and tidy wiring

What Can Be Done to Prevent Imbalance?

What to do

  • Correct float tension: The voltage of the charger must be adjusted according to the value and temperature in the battery manufacturer's data sheet.
  • Regular block-by-block measurement: Instead of just looking at the total stress, the float tension of each block should be periodically recorded and monitored as a trend.
  • Temperature Balance: The battery rack and chamber should be ventilated to remain at the same temperature; a block should be prevented from being close to the heat source (Battery Room Ventilation and Safety, Battery cabinet and assembly).
  • Arraying with batteries of the same model and age: Using batteries of the same age from the same production batch maintains balance.
  • Periodic Testing: Voltage measurement alone is not enough; internal resistance, condition and capacity tests should be planned together (What is a UPS battery test).
  • Complying with BMS settings and manufacturer recommendation on lithium: The charging voltage, current limit, and full charging interval should be established according to the manufacturer's recommendation.

Don'ts

  • Raising the total voltage of the charger on its own because one block has low voltage. Other blocks overcharge.
  • Attempting to charge a single cell or block with the string connection open; at high DC voltage, there is a risk of arcing and short circuit.
  • Adding a single new battery to an old string and assuming the problem is solved.
  • Trying to save a swollen, leaking or very hot battery with an equalization charge.
  • Disabling the lithium BMS or adding cells without manufacturer approval. This is directly related to occupational safety and fire safety.

For occupational safety and working rules Occupational safety in UPS and battery work Read the article as well.

In Which Situation Should Service Be Called?

If you have one of the following situations, get support from an authorized technical service instead of intervening on your own:

  • The difference between block voltages is growing over time.
  • A block is constantly hot, bulging or leaking.
  • After equalization charging, the same block deviates again.
  • The UPS gives shorter autonomy than expected in the last few tests.
  • The lithium pack's BMS repeatedly fails or cuts off charging prematurely.
  • The age of the battery pack is nearing the end of its manufacturer's life.

For what to expect during the service process UPS technical service process letter, for what the replacement cost depends on Factors Determining Battery Pack Replacement Cost The article helps.

Common Mistakes and the Right Approach

Common mistakeWhy the problem?The right approach
Just looking at the total array tensionDeviation between blocks is invisibleBlock-by-block measurement and recording
Making equalization charging as frequent as routine "refinement"High voltage can dry out the batteryOnly under the condition specified by the manufacturer, with the specified value
Thinking that every imbalance is a "balance problem"An old or damaged block does not improve with equalizationDistinguish by internal resistance and capacity test
Relying solely on total voltage in lithiumIn LiFePO4, cell difference is hidden due to flat curveMonitor BMS cell voltage data
Setting up arrays with batteries of different agesCharge distribution is constantly deterioratingUsing batteries from the same batch, the same age

How to Set Up a Balancing Plan in Backup Power Systems

Balancing is not a one-time task, it's part of a maintenance plan. If the system is critical to business continuity, this approach works:

  1. Create an initial record: Block voltages, internal resistance, and ambient temperature are recorded at commissioning (UPS initial commissioning and acceptance tests).
  2. Take periodic measurements: The frequency of measurement is determined by the battery type, criticality and manufacturer recommendation. The results should be compared as a trend.
  3. Define threshold: What to do in which deviation (re-measurement, equalization, test, change) should be determined in advance.
  4. Make the test plan according to the risk of downtime: Note that backup protection will be reduced during capacity testing (How to schedule a battery pack test).
  5. Report: The service report should include block-based values, the action taken and the recommendation (How to read a UPS maintenance report).

The same logic applies to solar or hybrid storage systems; for health checks in the battery bank of such systems Capacity and health test on solar battery bank, for cell-based monitoring BMS inscription links.

Technician wearing gloves and work clothes filling checklist during battery maintenance

Get Your Battery Bank Checked with Bempower

You can benefit from Bempower's exploration, installation, periodic maintenance and technical service for measurement of block voltages in battery groups, internal resistance and capacity tests, equalization charging and battery replacement when necessary. We provide on-site service in Istanbul and surrounding provinces. To find out the status of your current array From our contact page You can contact us.

  1. Safety, Storage, Operating and Maintenance Manual VRLA Battery Systems — EnerSys, 2008. https://www.enersys.com/493c0d/globalassets/documents/product-documentation/powersafe/_multi/amer/us-vr-om-002_0308.pdf
  2. VRLA Valve Regulated Lead Acid Batteries – User Manual — WEG, 2024. https://static.weg.net/medias/downloadcenter/hb2/h4a/WEG-VRLA-batteries-user-manual-10005922959-en.pdf
  3. A New Method for Maintaining the Charge of VRLA Batteries in Telecommunications Standby Systems — Battery Power Online, 2014. https://www.batterypoweronline.com/markets/batteries/a-new-method-for-maintaining-the-charge-of-vrla-batteries-in-telecommunications-standby-systems/
  4. A New Method for Maintaining the Charge of VRLA Batteries (BATTCON 2014) — Vertiv, 2014. https://www.vertiv.com/48dd1a/globalassets/documents/battcon-static-assets/2014/a-new-method-for-maintaining-the-charge-of.pdf
  5. Dissipative vs. nondissipative balancing (a.k.a.: Passive vs. Active balancing) — Li-Ion BMS, 2024. http://liionbms.com/php/wp_passive_active_balancing.php
  6. Passive Balancing Method for Electric Vehicles Using STM32f103C8 (AKÜ FEMÜBİD 20, DOI: 10.35414/akufemubid.691456) — DergiPark – Afyon Kocatepe University Journal of Science and Engineering, 2020. https://dergipark.org.tr/tr/download/article-file/1172615
  7. Investigation and Design of an Active Cell Balancing System for Li-ion Batteries — DergiPark – Journal of Engineering Sciences and Design, 2019. https://dergipark.org.tr/en/pub/jesd/article/553295
  8. Review on battery management systems and cell equalization (passive and active balancing) — DergiPark, 2023. https://dergipark.org.tr/tr/download/article-file/1639473

Resources

Frequently Asked Questions

01What is battery balancing?
Battery balancing is the process of bringing the state of charge and voltage of batteries or cells connected in series closer to each other. In a series array, the same current flows through all elements, but each element has different capacity, internal resistance and self-discharge. Without balancing, the weak element will discharge prematurely or overcharge, reducing the usable capacity and life of the entire group.
02Why is the voltage unequal in batteries connected in series?
Manufacturing tolerances, temperature differences, different internal resistances, different self-discharge rates, and aging levels distribute stress unevenly. In float charging, some are undercharged and some are overcharged because the total voltage is shared between the elements. The small difference tends to grow over time; therefore, measurement and correction charging should be done when necessary.
03What is the difference between passive and active balance?
In passive balance, the excess energy of the highest charged cell is converted into heat by resistance; the circuit is simple and inexpensive, but it operates with low current and consumes energy. In active balance, energy is transferred from the high-charge cell to the low-charge cell by a capacitor, inductance, or converter. It may be faster and more efficient, but the circuit is more complex and costly.
04What is equalizing charge and when is it done?
Equalization charging is a special charge made with a higher constant voltage for a certain period of time to eliminate the voltage imbalance in the lead-acid battery string that has been in the float for a long time. Voltage and duration vary by manufacturer. The battery manufacturer's manual should be consulted for the conditions and values under which it will be applied, and the process should be carried out by authorized technical personnel.
05Do UPS batteries (VRLA) have a cell balancing circuit?
Conventional lead-acid VRLA UPS batteries usually do not have a cell-based BMS balancing like lithium; balancing is achieved by the charger's correct float voltage, temperature balance, and periodic measurement. External battery stabilizer modules may be used in some projects. You can find out if your current system has such equipment from the technical service.
06Would it be enough to replace a single battery in an unbalanced battery group?
Often it is not enough. Since new batteries and aged batteries have different capacities and internal resistance, the voltage distribution may deteriorate again. The decision is made based on the age of the group, the remaining life and the test results. In general, it is not recommended to add a single new battery to an old group; it is necessary to make the evaluation with the battery test results.
07Can the user balance lithium batteries?
In the case of a lithium battery, balancing is normally done automatically by the BMS; no user intervention is required. However, if the system operates at continuous partial charging, the opportunity for passive balancing may be reduced and an occasional full charge may be required. Operations such as opening and charging cells individually are risky; in the case of high-voltage packs, only authorized technical personnel should do so.
08How much is the voltage difference in the battery group?
The acceptable limit varies depending on the battery type, manufacturer, and measurement condition; there is no single exact value. In lead-acid, manufacturers require the float voltage to remain within a certain band around the nominal value; if the difference between the block voltages grows over time, it is a warning sign. The limits should be based on the relevant battery data sheet and maintenance manual.
Bempower https://www.bemenerji.com/en/blog/what-is-battery-balancing-voltage-equalization-in-series-battery-groups
Write via WhatsApp