What is a Power Supply? AC-DC, DC-DC, and Switching Power Supplies
A phone charger, a metal box inside a computer, a 24V source in a PLC panel, or a rectifier in a telecom rack: they all do the same basic job. They convert energy into a form that the device can actually use, which is the right voltage and current. The power supply is often the part of the system that is least talked about, but stops everything when it fails.
This guide; explains what a power supply is, how AC-DC and DC-DC conversion is done, the difference between linear and switched (SMPS) structure, selection values such as efficiency and power factor, and safety documents in plain language. It was written for home users, business owners, technical responsible and purchasing units. Numerical examples are given with assumptions.
What is a power source and what does it do?
Power supplyis a device that provides the electricity it receives from an energy source (mains, battery, generator) at the voltage, current and quality required by the load. This definition covers four separate tasks:
- Conversion: Changes the type (AC to DC) or level (48 V to 12 V) of voltage.
- Regulation: It tries to keep the output constant even if the mains voltage fluctuates or the load changes.
- Insulation: In many designs, it provides electrical insulation between the input and output; thus, the person touching the output side or the connected circuit is separated from the grid.
- Protection: It limits or interrupts the output in overcurrent, short circuit, overvoltage and overheating.
The power supply and the UPS are often confused. A UPS is a system that maintains the output with battery energy when the mains is cut off; it also has converter floors inside. For this topic's own page What is UPS You can look at the article. The focus here is on power supplies that work alone and mostly output DC.

How does an AC-DC power supply work?
The AC-DC power supply converts the alternating voltage from the mains (230 V, 50 Hz in single phase in Turkey) to the correct voltage used by the device. Adapters, computer power supplies, LED drivers and panel type 24 V sources are in this group.
The simplified flow of today's common switching AC-DC source is as follows:
- Inlet filter and rectifier: It filters out interference, straightens AC with bridge diodes.
- Main capacitor: It flattens the rectified voltage to a high-value DC.
- Switching Floor: This high DC can be quickly switched on and off with a transistor. converting high-voltage AC to high-voltage DC and then back to AC to produce low-voltage DC It creates a structure that works through.
- High frequency transformer: It reduces voltage and provides insulation between input and output.
- Secondary straightening and filter: The high-frequency AC is rectified by the diode on the secondary side and flattened by the capacitor, converting to the target DC, such as 12 V.
- Feedback: The output voltage is measured continuously; the control circuit sets the transistor's on-time. In insulated designs, this information is often carried by an element such as an optocoupler.
The most common structure in low and medium powers flyback (returnable) converter. When the transistor is in conduction, the transformer stores energy magnetically, when the transistor is interrupted, this energy is transferred from the secondary winding to the output. Flyback is a structure that is accepted as a standard in applications where a low-cost and insulated solution is required. Sources usually indicate that it is recommended for powers below about 250 W; other topologies with higher power are preferred.
What is a DC-DC converter?
A DC-DC converter is a power source whose input and output are both the correct voltage. It is fed from the battery, rectifier busbar or an intermediate DC line and produces another DC level. Typical examples are obtaining 12 V or 5 V from a 48 V line in telecom fields, converting 24 V to 12 V in vehicles or caravans, and extracting a 5 V logic supply from 24 V in industrial panels. For detailed information What is a DC-DC converter and where is it used You can take a look at our article.
There are three basic switched DC-DC structures:
| Structure | What does it do? | Example usage |
|---|---|---|
| Buck (reducer) | It lowers the voltage in the same polarity; for example, it can convert +12 V to +5 V. | Generating 12V or 5V from a 24V line |
| Boost | It raises the voltage; the current drawn from the input is greater than the output current. | Generating 5 V from a single-cell battery, raising solar panel voltage |
| Buck-boost | It can produce output below or above the input; there are also varieties that can reverse the output polarity. | Places where constant output is required when battery voltage varies a lot |
| Isolated (e.g., flyback, forward) | It separates the input and output with the transformer galvanically. | Measuring circuits, long line feeds, safety requirements |
What buck and boost structures have in common is that they do the conversion by carrying energy through a coil and capacitor. Since the coil and capacitor do not consume energy, the loss comes mainly from the resistance of the switches and the diode drop. Therefore, the efficiency of switching converters is in practice. It can go up to 95-99 percent ; The actual value varies according to power and design, the manufacturer data sheet should be consulted.

Difference between linear power supply and switching power supply (SMPS)
The main difference between the two structures is how the output is arranged. In linear welding, a transition transistor continuously converts the voltage difference between the input and output into heat, keeping the output constant. In SMPS, on the other hand, The transistor quickly switches between full conduction and full cutoff by changing the duty cycle. Since the transistor is either fully open or fully closed most of the time, the power consumed on it decreases.
Detailed comparison of the two structures Linear and switching power supply differences article. Summary table:
| By | Linear | Switched (SMPS) |
|---|---|---|
| Performance | As the entry-exit difference grows, it decreases; if the difference is large, it can often remain below 60 percent. | Typically 80-95 percent and above; see manufacturer data sheet |
| Size and weight | It requires a 50/60 Hz transformer; it is large and heavy. | It uses high frequency small transformer; it is compact and lightweight. |
| Output noise | Very low ripple, calm output | Produces switching-induced ripple and EMI; filter is required. |
| Warm-up | High; coolant required. | Lower; but it still needs a share in a hot environment. |
| Input range | Narrow; mostly designed for single tension. | Wide input (e.g., 90-264 V AC) is common. |
| Typical use | Laboratory, precise analog measurement, some audio circuits | Adapter, computer, industrial boards, LED, telecom |
Efficiency in resources is switched in the range of 80-99 percent regardless of input-output voltage difference It is seen that it is given. This wide range depends on power, load ratio and design; each product should have its own data sheet as a basis.
Calculation example: same exit, two different losses
Assumptions: 24 V and 10 A (240 W) output are required. The throughput of the switched source is 90 percent, the typical efficiency of the linear solution is 60 percent; these are sample values.
- SMPS: Input power = 240 W ÷ 0.90 ≈ 267 W. Heat loss ≈ 27 W.
- Linear: Input power = 240 W ÷ 0.60 = 400 W. Heat loss = 160 W.
There is a difference of approximately 133 W between two sources doing the same job. In a system that operates continuously, this difference is reflected in the panel temperature as well as the electricity bill. Removing 160 W of heat in the panel also requires cooling.
The DC-DC equivalent of the linear regulator
The same logic applies on the DC-DC side. Suppose you want to produce 24 V and 12 A output from 2 V.
- Linear regulator: Loss = (24 − 12) V × 2 A = 24 W. Since the output is 24 W, the efficiency is about 50 percent.
- Buck converter (assuming 95 percent yield): Input ≈ 24 W ÷ 0.95 ≈ 25.3 W, loss ≈ 1.3 W.
If the input and output are close to each other (e.g. from 3.7 V to 3.3 V), the efficiency of the linear solution is also high; in this case, simplicity and low noise can take precedence.

Why is power factor correction (PFC) important?
A simple input stage consisting of a rectifier and a capacitor draws the current from the mains in short and pointed pulses. Since this current is not in the form of sinus, The power factor can go down to as low as about 0.6. The result is higher current and more harmonics to draw the same real power. Thread What is the power factor We explained it fundamentally in the article.
There are two ways to fix it:
- Passive PFC: A large coil is placed on the input side. It is simple and quiet, but the gain is limited; The power factor remains at around 0.75, and harmonic requirements are met only to a limited extent.
- Active PFC: An additional ply, based on the boost structure, shapes the input current to follow the voltage. With this structure, a power factor of over 0.98 can be achieved.
IEC/EN 61000-3-2 standard, which applies to single-phase devices in Europe, It determines the upper values of the current components drawn from the second harmonic to the 40th harmonic. The standard does not directly say "there should be this much power factor"; It determines harmonic current limits, it does not set a separate lower limit for power factor. In other words, it is not enough information for the data sheet to say only "PFC present"; it should be looked at which power factor is provided at which loads. For the scope and classes of the standard that the entry covers equipment 16 A and below it is enough to know; refer to the IEC's current publication for class details.
Calculation example: input current
Assumptions: output 24 V × 6 A = 144 W, efficiency 90 percent, power factor 0.95, mains 230 V.
- Input actual power = 144 W ÷ 0.90 = 160 W
- Apparent power = 160 W ÷ 0.95 ≈ 168 VA
- Input current = 168 VA ÷ 230 V ≈ 0.73 A
If the power factor were 0.6, the apparent power would be approximately 267 VA and the current would be approximately 1.16 A for the same load. This difference directly affects the capacity requirement when supplying the source with a generator or UPS.
What criteria should be considered when choosing a power supply?
Reducing the selection to a single value (mostly Watts) is a common mistake. The table below can be used as a step-by-step checklist. To drill down into industrial applications Choosing an industrial power supply See the article.
| By | What to look for? | Common mistake |
|---|---|---|
| Output voltage | Rated stress and tolerance of the load; adjustment range if necessary | Choosing an "approximate" tension without taking into account the wide tolerance range of the load |
| Output current / power | Sum of all loads + about 20-30 percent share; high take-off currents | Collecting plate power and leaving no margin |
| Input range | Mains voltage tolerance, supply status with generator or UPS | Using the product with a narrow input range in a fluctuating network |
| Yield and idle consumption | Efficiency at rated load and partial load, no-load drawn power | Just looking at the peak yield value |
| Protection | Overcurrent, short circuit, overvoltage, overheat | Not checking the way the protection mode restarts (hiccups, locks) |
| Operating Temperature | High temperature derating curve | Thinking the temperature inside the panel is room temperature |
| Power factor / PFC | What value is provided at which load rate? | Relying solely on the phrase "PFC" |
| Documents | CE, relevant safety and EMC standards, manufacturer's statement | Using products that come without documents or with duplicate documents |
Calculation example: how to determine welding power?
Assumption: A panel that works with 24 V; There is a relay and sensor group that draws 3 A, two small motor drive feeds that draw 4 A, and an HMI with 1 A. All of them work continuously.
- Total current = 3 + 4 + 1 = 8 A
- Total power = 24 V × 8 A = 192 W
- With a share of 25 percent = 192 × 1.25 = 240 W
- Source to choose: 24 V and 10 A (240 W) class. If the panel temperature is high, a higher level is considered according to the derating curve.
The margin is not just because there is room for growth. A source that is constantly running at full load heats up more, which reduces capacitor life. Leaving some headroom for the load improves reliability.
Safety documentation and legislation: CE, IEC 62368-1 and efficiency
A power supply powered by the mains has high-voltage internals, so safety compliance is a technical requirement, not a marketing one.
- Low voltage legislation (LVD): Regulation, It covers electrical equipment designed to be used between 50-1000 V in alternating current and 75-1500 V in direct current. For products within this scope, the manufacturer makes conformity assessment and CE marking with EU declaration of conformity required. For this reason, CE marking and declaration of conformity are expected for a power supply with an input of 230 V; although the output side of the source with an output of 24 V is below these thresholds, the device is covered due to the input voltage.
- IEC 62368-1: Audio-video is the safety standard for information and communication technology equipment. Classifies energy sources and defines the protection measures to be taken against them. The standard is not only for the finished product; to the sources mounted inside the device and the external adapters that come with the device is also applied. You can ask the manufacturer on the label of the product you have been tested according to which standard version.
- Harmonic and EMC: Standards such as IEC 61000-3-2 described above limit how much the source disrupts the grid.
- External power supply efficiency: Plug-in adapter class products have energy efficiency regulations. In the U.S. An external power supply is defined as the circuit that converts residential electricity to DC or low-voltage AC and drives a consumer product. In Türkiye, a communiqué on external power sources was published in the Official Gazette dated October 16, 2026; Among the definitions in the communiqué are "low-voltage external power supply" with an output voltage of less than 6 V and an output current of 550 mA and above. For the scope, effective date and obligations, see the current text of the communiqué and the official announcements of the relevant Ministry; no details are provided in this article.
Legislation and standard versions change over time. If you are preparing a purchase specification, verify the current texts on the official pages of the relevant institutions.
The difference between a power supply and a battery charger, rectifier and UPS
These devices are similar to each other, but they are not the same. They all have a transducer; the difference is in how the output is managed.
| Device | How does it manage output? | Typical task |
|---|---|---|
| Power supply | It gives constant voltage (and current limit). | Feeding the load |
| Battery charger | It changes voltage and current according to the charging phase of the battery. | Filling the battery with the correct profile |
| Rectifier | While feeding the load, it also holds the battery with float voltage. | Telecom, power plants, DC panels |
| UPS | When the mains is cut off, it continues to produce AC output from the battery. | Uninterrupted supply of AC loads |
It is inconvenient to use a simple DC power supply directly as a battery charger; the required charge profile for the battery cells is not provided. Reasons for the difference The difference between a battery charger and a DC power supply We explained it in the article. For the rectifier side The difference between rectifier and UPS would be useful. If DC loads need to be supplied uninterruptedly DC UPS solutions is a separate option.

Redundant power supply use
If the failure of a single source can stop the entire line, parallel redundant operation of two sources is considered in critical systems. In this logic, both sources are selected in a size that can carry the load alone and the outputs are combined through the diode or redundancy module. Thus, even if one fails, the other maintains the load.
Here are the considerations for redundancy to work:
- The outputs are not directly connected to each other; a separator diode or redundancy module is used.
- It is verified by calculation that each resource alone can meet the entire load.
- Ideally, two sources are fed from a different input line; otherwise, the redundancy ends at a single network point.
- The fault signal (alarm contact) is monitored because the silent failure of one eliminates redundancy unnoticed.
Detailed explanation of the subject Redundant Power Supply Systems It is in the article.

Why do power supplies fail and how to use them for a long time?
The component that determines the life of the power supply the most is usually the electrolytic capacitor. As the temperature rises, the electrolyte loss of the capacitor accelerates. Therefore, heat management is the main condition for long life.
| Symptom | Possible cause | The first safe step |
|---|---|---|
| There is no exit at all | No input, blown fuse, internal fuse or control floor failure | Check the input supply and panel fuse; do not open the contents. |
| Output voltage low or fluctuating | Overload, aged capacitor, input voltage drop | Measure the load current, compare the total load with the rated current of the source. |
| Welding on and off (hiccup) | Short circuit or overload protection, load side failure | Separate the load, try the source alone; if the fault is in the load, look for it from there. |
| Overheating | Blocked ventilation, high ambient temperature, fan failure, dusting | Check the ventilation gap and board temperature. |
| Sound (buzz, sizzle) | Coil or transformer vibration, degraded components | If the volume changes with load, report it to the service. |
On the maintenance side, simple rules are often sufficient: maintain the air gap specified by the manufacturer around the weld, have dust removed from the enclosure periodically, do not run the welds near the rated power all the time and have hot spots checked with a thermal imager if necessary. For more detailed fault symptoms and a repair-or-replace decision Power supply failures and repair decision You can look at the article.

Safety: what to look for when working with a power supply?
A power supply connected to the mains has high-voltage sections inside. Even after the device is unplugged, large capacitors can carry a dangerous load for some time. The following rules are therefore important:
- Do not open the cover and interfere with the internal circuit; this job belongs to trained technical service or authorized electrical personnel.
- Carry out connection and disassembly work in a de-energized and verified state.
- Just because the output side is "undervoltage" doesn't mean the entire device is safe; the input side is at mains voltage.
- The cable cross-section, fuse rating and ground connection must comply with the device's label and relevant plumbing codes.
- Short-circuit current can be very high in battery-connected DC systems; insulated tools and protective equipment should be used against the risk of arcing and burns.
- If you see a suspicious odor, swollen capacitor, blackening or excessive temperature, disconnect the appliance from energy and report it to the service.
Occupational safety topics for UPS and battery environments in general, not for power supply Occupational safety in UPS and battery work It is discussed in the article.
Which power supply in which case?
- Electronic device or printer adapter: The original or equivalent (voltage, current, connector polarity) adapter of the device. Using a "universal" adapter with a mismatched voltage may break the device.
- Enclosure and automation (24 V DC): DIN rail type, switched, wide input range, protection features specific power supply; redundant on critical lines.
- Battery-assisted DC loads: Rectifier or DC UPS.
- Where different voltage is required from the battery line: Insulated or non-insulated DC-DC converter; according to battery voltage and load current.
- Measurement and laboratory: Linear or hybrid welding with linear output if low noise is required.
In none of these is the "strongest is the best" approach; need and working condition are decisive.
Technical support on power supply
Power supply failure or capacity problem is often an issue that needs to be considered together with the backup system. If you need exploration, installation, periodic maintenance and technical service on the UPS, battery pack and inverter side From our contact page You can reach out to the Bempower team. We offer on-site services in Istanbul and surrounding provinces.
- IEC 62368-1:2018 – Audio/video, information and communication technology equipment – Part 1: Safety requirements — IEC Webstore, 2018. https://webstore.iec.ch/en/publication/27412
- IEC 62368-1: An Introduction to the New Safety Standard for ICT and AV Equipment — Bel Fuse, 2020. https://www.belfuse.com/resource-library/tech-paper/iec-62368-1-an-introduction-to-the-new-safety-standard-for-ict-and-av-equipment
- Energy Conservation Program: Test Procedure for External Power Supplies — Federal Register / U.S. Department of Energy, 2022. https://www.federalregister.gov/documents/2022/08/19/2022-15975/energy-conservation-program-test-procedure-for-external-power-supplies
- Official Gazette, 16 October 2026 (communiqué on external power sources) — Official Gazette of the Republic of Turkey, 2026. https://www.resmigazete.gov.tr/eskiler/2026/10/20261016-14.htm
- Low Voltage Directive (LVD) 2014/35/EU – regulation text and scope — Eksen Certification (regulation text transfer), 2024. https://www.eksenbelgelendirme.com/alcak-gerilim-yonetmeligi-lvd-2014-35-eu
- Flyback converter design considerations — Texas Instruments, 2023. https://www.ti.com/lit/pdf/ssztcu9
- An Introduction to Flyback Converters: Parameters, Topology, and Controllers — Monolithic Power Systems, 2024. https://www.monolithicpower.com/en/learning/resources/an-introduction-to-flyback-converters-parameters-topology-and-controllers
- Isolated Flyback Converter Basics: What is Switching AC-DC Conversion? — ROHM Semiconductor, 2015. https://techweb.rohm.com/product/power-ic/acdc/846/
- Switch mode power supply (SMPS) — Analog Circuit Design, 2023. https://analogcircuitdesign.com/switch-mode-power-supply/
Resources