Unbalanced Voltage and Terminal Corrosion in the Battery Bank
The battery group of the UPS consists of batteries connected in series: the same current flows through all of them, the voltages are collected. In a newly installed group, the voltages of the batteries are very close to each other. Over time, these values diverge; one or more batteries remain significantly lower (or higher) than the others. This is called voltage unbalance.
Imbalance is not a failure on its own; it is an indication that something has changed within the group. A situation that can be solved with a single battery change if detected early takes the whole group away when it is late.
What Causes Imbalance?
| Cause | How to recognize | What to do |
|---|---|---|
| Difference in the aging of batteries | A battery's voltage is consistently low, its internal resistance is high | Group change is planned |
| Temperature difference | Batteries on the top row of the rack or close to the wall are warmer | Layout and ventilation are corrected |
| Loose or oxidized connection | In the measurement, the battery itself is normal, the voltage difference in the interconnection | It is cleaned, tightened with the torque given by the manufacturer |
| Different date/party | The battery added later differs from the others | The group is replenished with the same batch of batteries |
| Charging circuit problem | The float voltage of the whole group is out of the range given by the manufacturer | The charging circuit of the UPS is checked |
Polar Head Corrosion
The whitish or greenish layer formed on the terminals increases the resistance of the connection. The consequences are:
- The junction heats up under load; the heated point deteriorates further over time.
- In the measurements, that battery looks worse than it is; the problem is actually in the contact.
- If it takes a long time, the terminal and cable lug will be permanently damaged.
After the corrosion-infested connection, UPS, and battery pack are safely disabled, they are cleaned, inspected, and re-tightened to the manufacturer's specified torque. Work on the battery is done with an insulated tool, goggles, and gloves; metal jewelry is removed. Terminal cleaning is a standard step in periodic maintenance — checklist How to maintain a battery You can find it in our article.
How to Measure?
- Voltage per battery: When the group is on float charge, the voltage of each battery is measured and recorded individually.
- Comparison: The values are compared with each other and with the float range given by the manufacturer; decomposing batteries are marked.
- Internal resistance: Although the voltage appears normal, the internal resistance may be elevated; the measurement is taken at the same maintenance.
- Links: The voltage drop on the interconnections is measured to find a loose or oxidized point.
- Temperature: The surface temperatures of the batteries are compared; a significant difference indicates a placement or connection problem.
What the internal resistance value indicates What is battery internal resistance?, how temperature differences are captured in the image. UPS control with thermal camera We explained it in our article. The real duration of the group is alone with discharge test is seen.
When a Weak Battery Is Found
If a single battery is decomposed, the first thing that comes to mind is to replace it. However, when the new battery works in the same group with the aged batteries, it quickly descends to their level; the group again gives the duration of the weakest battery. Therefore, the time elapsed after the first installation is considered: if the group is new, a single replacement can be considered, if it is over a certain age, the entire group is renewed. Details of the decision Should a single battery or the whole group be replaced? We explained it in our article.
If the imbalance is left uncorrected, the weak battery will first discharge on discharge, and on charge it will be overcharged while the others are filled; this is where heating and swelling begin. Symptoms What causes battery swelling You can find it in our article.
What Does Voltage Unbalance Indicate?
Batteries in the series group carry the same current; the separation of their voltages indicates aging, temperature or connection difference.
First, the connection and temperature are eliminated, then the battery itself is checked. If the measurement record is not kept, it cannot be understood when the change started.
Frequently Asked Questions
01How much difference is normal between batteries?
02Will an unbalanced battery bank ruin a UPS?
03Can I clean the white film on the terminal myself?
04How often should measurements be taken?
05Does a balancing device solve the problem?
Let's Measure Your Battery Group
In periodic maintenance, voltage and internal resistance measurement per battery, connection control and temperature comparison are our standard steps; the results are given in the report with their values. Scope Periodic Battery and UPS Maintenance On our page, we take the test that measures the real time of the group. Discharge and Load Tests page. The brand of your UPS and the number of batteries Send us, let's set the day for measurement.