How to Read a UPS Maintenance Report? What Information Should It Include?

How to Read a UPS Maintenance Report? What Information Should It Include?

When the maintenance visit is over, you are left with a report of several pages. Most of the time, the "overall result" line at the bottom is looked at and the report is removed to the file. However, the real value of the report is in the measurements and the change seen when placed side by side with the next report.

What is looked for in maintenance UPS maintenance checklist We explained it in our article. In this article, we explain what information should be included in a maintenance report and how to read this information.

Sections of the Report

The format of the reports varies from company to company; but it is expected to contain the following sections in terms of content:

EpisodeContent
General informationAppliance, model, serial number, location, date and type of visit, technician performing maintenance
Environment and visual controlRoom temperature, ventilation, dust, external appearance of the device and batteries
Electrical measurementsInput and output voltage, frequency, current, load ratio
Battery measurementsVoltage, internal resistance, temperature and result per battery
Event recordingAlarms, transitions to battery and bypass since the last visit
Tests and processesFunction tests, cleaning, tightened connections, replacement parts
Findings and recommendationsProblems seen and recommended work to be done
ConclusionGeneral condition of the system and the date of subsequent maintenance

If there are only lines in the report that say "suitable" or "checked", it is appropriate to request the measured values as well. A check without a value cannot be compared in the next maintenance.

Electrical Measurements and Load Rating

Input values indicate the status of the network, and output values indicate what the UPS is supplying to the load. The output voltage and frequency must be stable even if the input fluctuates.

Load Ratiois the ratio of the connected load to the UPS power. In practice, it is recommended that the UPS should not be loaded more than roughly 70-80% of its power continuously; this share covers the sudden loads at the time of departure and the devices to be added in the future. This is not a definite limit, but a design margin; the main thing is the manufacturer's recommendation. In redundant (parallel) systems, when one device is disabled, the ratio per device is kept lower because the others must be able to carry the entire load. How this share is used in power calculation How to calculate UPS power We explained it in our article. In three-phase systems, the load distribution between phases is also checked. An increase in the load ratio between reports may indicate that new devices are connected to the UPS and the backup time is shortened.

Battery Chart: Voltage and Internal Resistance

The battery table is the most informational section of the report. Each battery is tracked by a number indicating its location in the array and is read from two directions:

  • With other batteries in the array: Batteries of the same type and age should give close voltage and internal resistance. The battery that differs significantly from the average is examined separately.
  • With the previous measurements: The value of internal resistance alone says little; it matters how much and how quickly it has changed since the initial measurement.

A weakened battery may also appear normal when the battery voltage is measured under charge; therefore, voltage alone does not indicate the health of the battery. How the values are interpreted What is battery internal resistance? In our article, we explain how the decision to change is made. When to replace a UPS battery We explained it in our article.

Temperature

Battery life is usually given for an ambient temperature of 20–25 °C; if the room temperature is consistently above this in the reports, the batteries may age earlier than expected. If one of the batteries is significantly hotter than the others, that battery or its connection is examined separately. During visits to thermal camera checks, images of hot spots are also added to the report; how they are read Thermal camera control We discussed it in our article.

Event Recording

The event log describes what happened between two visits. In the summary in the report, see:

  • The number of times the battery is switched; an increase in the number may indicate a problem with the network or input settings
  • Transitions to bypass and their causes
  • Overload and over-temperature warnings
  • Failed battery tests

The dates of the events only make sense if the device's clock is correct. Therefore, it should be seen in the report that the UPS clock has been checked; in this way, it can be checked whether the switches to the battery coincide with known interruptions in the network.

Language of Suggestions

A good report writes not only about the problem, but also about what needs to be done and how urgent it is. Recommendations can be read roughly on three levels:

ExpressionMeaning
Must WatchNo problem yet; the value will be remeasured and compared at the next maintenance.
Should be plannedWork is necessary but not urgent; tasks such as battery replacement should be included in the budget and calendar.
EmergencyA problem that affects the safety of the system or its ability to carry the load; It should be addressed without waiting.

If there's a statement you don't understand or a suggestion with no justification, don't hesitate to ask the maintenance team.

Reading Reports Side by Side

The value of a report is revealed when it is compared to the previous one. When the new report comes in, ask these three questions: Which batteries have started to differ from the others? Has the load ratio and the number of battery switches changed? Which of the previous report's recommendations have not yet been made?

In our maintenance plans, a detailed report of each visit is stored in My Account → My Devices and Maintenance; comparison is made easy because historical reports are in one place. How reports affect maintenance frequency UPS maintenance frequency and maintenance schedule We explained it in our article.

Maintenance Report at a Glance

A good UPS maintenance report has eight sections, from general information to recommendations.

Writing down the measured values and reading the reports side by side allows battery replacement and part replacements to be planned based on the measurement.

Frequently Asked Questions

01All values appear to be "appropriate" in the report; are the batteries intact?
A single report is not enough to show this. The condition of the batteries is determined by how the values have changed compared to previous measurements. Make sure that the measured values are printed in the report.
02Battery voltages are normal, but internal resistance has increased; what does this mean?
Voltage indicates the state of charge of the battery, not its aging. A significant increase in internal resistance compared to the initial measurement may be an early sign that the battery is weakening; the condition of the battery is evaluated separately.
03Why is load ratio important?
As the load increases, the backup time of the UPS decreases and the risk of overload increases. An increase in the load rate between reports may indicate that new devices are connected to the UPS.
04Should I keep old reports?
Yes. The status of the batteries and the device is only understood when the reports are placed side by side. The reports of our maintenance plan customers are stored in My Account → My Devices and Maintenance.
05What should I do if there is a recommendation in the report that says "urgent"?
Talk to the maintenance team immediately and don't wait for the next maintenance day. Such recommendations may affect the safety of the system or its ability to bear the load in the event of an outage.

Let's Evaluate Your Report Together

We perform periodic maintenance for UPS and battery systems of all brands and models throughout Istanbul and in the surrounding provinces; in our maintenance plans, a detailed report of each visit is stored on your My Account page. Scope of the maintenance visit Periodic Battery and UPS Maintenance, plans Care Plans You can find it on our page. If you have questions about the report you have, Send us.