12 V 8 Ah high current maintenance-free dry type (VRLA-AGM) battery for UPS, alarm, emergency lighting and security systems. No water or acid additions required; 8 years design life in buffer use.
-
CE
- UL
- ISO 9001
- ISO 14001
- OHSAS 18001
Ritar HR12-32Wis a 12 V 8 Ah dry type battery produced with valve-regulated lead acid (VRLA) technology, with an electrolyte impregnated with glass fiber separators (AGM). It does not require the addition of water or acid, it does not require maintenance.
With its 151 × 65 × 100 mm dimensions, it is the same size as the 12 V 7–9 Ah class batteries commonly used in small power UPSs, alarm and fire panels, emergency lighting and security camera systems. Its poles are 6.35 mm faston (F2) type.
Ritar HR (High Rate) is the series designed to deliver high power in a short time: thanks to the reinforced grid, thick plate and special active material, it has low internal resistance and self-discharge, according to the manufacturer, it delivers about 30% more power than the standard series; it is suitable for high-power standby applications such as data center, UPS and EPS.
Where is it used?
12 V 8 Ah batteries, which activate when the power is cut off Standby (buffer) use Designed for: the battery is kept fully charged at all times while the device is connected to the mains, feeding the device in case of an outage.
- Uninterruptible power supplies (UPS) — linear interactive and online models
- Alarm and fire detection panels
- Emergency lighting and direction fixtures
- Security camera, recorder (NVR / DVR) and modem backup
- Automatic door, barrier and access control systems
- Backup supply of network and telecom devices
The 8-year design life in the datasheet is for buffer use. In cyclic use, which discharges and fills up every day, the life depends on the number and depth of discharge.
Our UPSs that use this battery
The following Bempower UPSs use batteries in the range of 12 V 7–9 Ah (some with 9 Ah); you can install this model when changing the battery. Batteries in a device togetheris replaced with the same model — the old and new battery are not mixed (Why?).
- Myon 600 VA Line Interactive UPS — 1 battery
- Myon 650 VA Line Interactive UPS — 1 battery
- Myon 1000 VA Line Interactive UPS — 2 batteries
- Myon 1200 VA Line Interactive UPS — 2 batteries
- Myon 1 kVA Rack / Tower Online UPS — 2 batteries
- Myon 2 kVA Rack / Tower Online UPS — 4 batteries
- Myon 3 kVA Rack / Tower Online UPS — 6 batteries
- Myon 6 kVA Rack / Tower Online UPS — 16 batteries
- Myon 10 kVA Rack / Tower Online UPS — 16 batteries
- Myton 1 kVA Online UPS — 2 batteries
- Myton 2 kVA Online UPS — 4 batteries
- Myton 3 kVA Online UPS — 6 batteries
- Myton 6 kVA Online UPS — 15 batteries
- Myton 10 kVA Online UPS — 16 batteries
- Myton 3110 10 kVA 3/1 Online UPS — 16 batteries
- Myon 3310 10 kVA Three Phase Online UPS — 20 batteries
- Myon 3320 20 kVA Three Phase Online UPS — 40 batteries
- Myon 3330 30 kVA Three Phase Online UPS — 60 batteries
- Myon 850 VA Line Interactive UPS — 1 battery
- Myon 1500 VA Line Interactive UPS — 2 batteries
- Myon 2000 VA Line Interactive UPS — 2 batteries
If you are buying for another brand of device, compare the voltage, size (151 × 65 × 100 mm) and pole type of the old battery; if you are not sure Ask Us.
How long does it last on UPS? (calculated, estimated)
The following times are manufacturer measurement It is not; From the discharge table in the data sheet of this battery Calculated Estimate values. Valid in a 25 °C environment with a new and fully charged battery.
| Total load connected to the UPS | Estimated time (single battery) |
|---|---|
| 25 W | More than 1.5 hours |
| 50 W | ~1.0 hours |
| 100 W | ~26 min |
| 150 W | ~15 min |
| 200 W | ~10 min |
How was it calculated? The constant power table in the data sheet (25 °C, 1.75 V cut-off per cell) was used; the inverter efficiency of the UPS when operating from the battery was considered to be 85%. In UPSs with multiple batteries, the load is divided among the batteries; those models have times calculated according to the number of batteries on their own page. Detail of the method: How to calculate battery time?
Manufacturer's discharge values (single battery, 25 °C, 1.75 V cut-off per cell — most UPSs disconnect at this voltage):
| Duration | Constant current | The power of the battery |
|---|---|---|
| 5 min | 29.5 A | 328 W |
| 10 min | 20.91 A | 235 W |
| 15 min | 15.87 A | 179 W |
| 30 min | 9.191 A | 105 W |
| 1 hour | 5,245 A | 60 W |
The actual time varies according to the age of the battery, the ambient temperature and the variability of the load; it is significantly shortened in aged batteries.
Choosing the right battery
- Voltage: 12 V. The voltage on the label of the battery in your device must be the same.
- Size: 151 × 65 mm base, 100 mm height with poles (± 1 mm). Fits in the battery compartment or cabinet shelf, the lid closes easily.
- Pole Type: 6.35 mm faston (F2). The female faston end on your cable should also be 6.35 mm; 4.8 mm leads will not fit on this pole.
- Capacity: If your UPS supports a range of 7–9 Ah, batteries in this range are suitable; as the capacity increases, the time increases, and the full charge time increases.
- Type: UPSs charge according to the dry type (VRLA-AGM) battery; the flooded (well-maintained) automobile battery is not installed in the UPS.
- Batteries in the array: It must be the same model and, if possible, from the same production date.
Charging, mounting and safety
- Standby (buffer) charging: 13.7 – 13.9 V at 25 °C, temperature correction –3 mV/°C per cell; –18 mV/°C per battery. UPSs and alarm panels make this setting themselves.
- Equalization Charge: 14.6 – 14.8 V at 25 °C, temperature correction –4 mV/°C per cell; –24 mV/°C per battery. If charging with a separate charger, use an AGM-set device that matches these values.
- Charging current: the highest charging current recommended by the manufacturer is 2.4 A.
- Assembly: switch off the device and disconnect it from the mains; do not connect the polarity backwards (red +, black –). Faston ends should fit all the way — loose contact will heat up.
- Short Circuit: The short-circuit current of the battery is 440 A. Do not touch the two poles with the metal tool at the same time, remove the ring and watch when inserting.
- Environment: Use the batteries in a ventilated location away from the heat source and direct sun.
Life, storage and change
- Design life: 8 years in buffer use. Real life; It depends on the ambient temperature, number and depth of discharge. Keeping the environment where the batteries are located at 20-25 °C preserves life.
- Temperature: the recommended operating temperature is 25 ± 5 °C; the battery ages faster in a hot environment, and the capacity it can give decreases in the cold.
- Storage: while the battery is unused, it discharges at most 3% per month at 25 °C; it should be kept for a maximum of 6 months and then refresh charged, more frequently in hot environment.
- Time to change: If the duration of the UPS has shortened significantly, if it gives a battery warning or if the battery is swollen, it is time for a replacement. When should a UPS battery be replaced?
- Waste battery: Used batteries are not disposed of in household waste; they are handed over to waste battery collection points.
Battery replacement and Periodic Maintenance With our services, we measure your batteries and replace them on time.
| Nominal voltage | 12 V |
|---|---|
| Nominal capacity | 8 Oh |
| Battery technology | VRLA – AGM (maintenance-free, dry type) |
| Design life | 8 year |
| Pole (terminal) type | 6.35 mm faston |
| Dimensions (L × W × H) | 151 × 65 × 94 mm |
| Total height (with pole) | 100 mm |
| Internal resistance | approximately 22 mΩ |
| Short circuit current | 440 A |
| Case material | ABS (UL94-HB; UL94-V0 optional) |
| Capacity | 8 Ah — reference capacity (C20) of 20 hours in the data sheet; the manufacturer classifies this model with a power rating of 15 minutes |
| Polar code (manufacturer) | F2 |
| Power rating (manufacturer) | 32 W/cell — up to 1.67 V per cell, 25 °C (192 W per battery) at 15 minutes of discharge |
| Reference capacity (25 °C) | C10 7.5 Ah · C20 8 Ah |
| Highest discharge current | 80 A (5 sec) |
| Peak charging current | 2.4 A |
| Standby (buffer) charging voltage, 25 °C | 13.7 – 13.9 V (temperature correction –3 mV/°C per cell; –18 mV/°C per battery) |
| Equalization charging voltage, 25 °C | 14.6 – 14.8 V (temperature correction –4 mV/°C per cell; –24 mV/°C per battery) |
| Operating temperature | Discharge –20 ... · 60 °C Charge 0 ° · 50 °C · Storage –20 °C °C |
| Recommended operating temperature | 25 ± 5 °C |
| Self-emptying | Up to 3% per month at 25 °C |
| Storage | Maximum 6 months at 25 °C, then refresh charge (more frequent in heat) |
| Dimension tolerance | ± 1 mm |
| Warranty | 2 year |
| Weight | 2,2 kg |
| Status | Zero |
| Stock | Sold out |
Batteries are delivered with their original pole protectors and without any connection to the poles. For withdrawal, the battery must not be used, charged/discharged and the terminals must not be connected; batteries that are installed and used will not be returned or will be deducted from the loss of value. Check the capacity and size suitable for your UPS before ordering; in case of wrong selection, the return shipping is your responsibility.
Delivery Process
- It will be shipped within 1–3 business days.
- The tracking number is shared by email and in My Account → My Orders.
- When picking, check the package with the cargo officer; if there is damage, make a report and do not receive it.
- Heavy and multi-volume shipments are delivered by warehouse or vehicle; the time and fee are shown according to your address in the payment step.
Returns and exchanges
- You can exercise your right of withdrawal within 14 days of delivery (individual purchases).
- The product to be returned must be unused, in its original packaging, complete with the invoice and accessories.
- Loss of value is deducted from products that have been installed and used, terminals connected or commissioned; if the use has made it impossible to return, the return will not be accepted.
- Return shipping cost belongs to the buyer; For defective, damaged or incorrectly sent products, the price belongs to us.
- Refunds will be made to your payment method no later than 14 days after the product has been received and inspected.
- The legal right of withdrawal does not apply to corporate (commercial purposes) purchases; requests are evaluated separately.
Customer reviews
There are no reviews for this product yet.
If you've used this product, share your experience—be the first to leave a review.
Rate this product
- Your rating and a few sentences will help guide other customers.
- You decide whether your name, city, and photo will be displayed.
- If you purchased it from us, the "Purchased" badge will appear in your review.
Log in to post a comment.