Blackbatt BC100-12 12V 100Ah AGM Battery
Blackbatt BC100-12 12V 100Ah AGM Battery
- Model code
- BC100-12
- Series
- Blackbatt BC
- Status
- Zero
- Stock
- Sold out
- Category
- 12V AGM Batteries
- Warranty
- 2 year
12V 100 Ah maintenance-free dry type (VRLA-AGM) battery for UPS battery cabinets, data center and telecom systems. No water or acid additions required; 10 years design life in buffer use at 20 °C.
-
CE
- UL
- TSE
- ISO 9001
- ISO 14001
- ISO 45001
Blackbatt BC100-12It is a 12 V 100 Ah dry type battery produced with valve regulated lead acid (VRLA) technology and its electrolyte is impregnated with glass fiber separators (AGM). It does not require the addition of water or acid, it does not require maintenance.
With a size of 330 × 173 × 220 mm and a weight of approximately 27.8 kg, it is used in UPS battery cabinets and racks, telecom and DC backup systems. Its poles are of the M8 bolt-on (T11) type.
Where is it used?
12 V 100 Ah batteries, which are activated when the power is cut off Standby (buffer) use Designed for: the battery is kept fully charged at all times while the device is connected to the mains, feeding the device in case of an outage.
- UPS battery cabinets and racks — long-term single-phase and three-phase UPSs
- Data centers and server rooms
- DC backup of telecom, base station and network systems
- DC supply of control/protection systems in power and substations
- Emergency lighting and fire centers
The 10-year design life in the datasheet is for buffer use. In cyclic use, which discharges and fills up every day, the life depends on the number and depth of discharge.
Which of our UPSs is used with?
For Bempower UPSs that work with an external battery bank, the battery bank can be installed with these batteries. The number of batteries in the group is determined by the battery voltage of the UPS; the capacity is selected based on the desired duration:
- Myon MYLONG-1000 1 kVA Online UPS (With Additional Charging Card) — 3-battery pack (36V)
- Myon MYLONG-2000 2 kVA Online UPS (With Additional Charging Card) — external battery pack
- Myon MYLONG-3000 3 kVA Online UPS (With Additional Charging Card) — 8-battery pack (96V)
- Myon MYLONG-6000 6 kVA Online UPS (With Additional Charging Card) — 16 or 20 battery packs (192 / 240 V)
- Myon MYLONG-10000 10 kVA Online UPS (With Additional Charging Card) — 16 or 20 battery packs (192 / 240 V)
- Myton 3110 KS 10 kVA 3/1 Online UPS (With Additional Charging Card, Without Battery) — 16 or 20 battery packs (192 / 240 V)
- Myon 3340 40 kVA Three Phase Online UPS — 32–40 battery groups
- Myon 3360 60 kVA Three Phase Online UPS — 32–40 battery groups
- Myon 3380 80 kVA Three Phase Online UPS — 32–40 battery arrays, parallel arrays for long periods of time
- Myon 33100 100 kVA Three Phase Online UPS — 32–40 battery arrays, parallel arrays for long periods of time
- Myon 33120 120 kVA Three Phase Online UPS — 32–40 battery arrays, parallel arrays for long periods of time
- Myon 33160 160 kVA Three Phase Online UPS — 32–40 battery arrays, parallel arrays for long periods of time
- Myon 33200 200 kVA Three Phase Online UPS — 32–40 battery arrays, parallel arrays for long periods of time
All batteries in a group must be of the same model, the same capacity and, if possible, the same date of manufacture; the old and new batteries must not be mixed (Why?). The right capacity for the time you need with power calculator or You can ask us.
If you are buying for another brand of device, compare the voltage, size (330 × 173 × 220 mm) and pole type of the old battery; if you are not sure Ask Us.
How long does it last on UPS? (calculated, estimated)
The following times are manufacturer measurement It is not; From the discharge table in the data sheet of this battery Calculated Estimate values. Valid in a 25 °C environment with a new and fully charged battery.
| UPS load per battery | Estimated time |
|---|---|
| 100 W | ~10.0 hours |
| 250 W | ~3.2 hours |
| 600 W | ~57 min |
| 1,000 W | ~26 min |
| 1,500 W | ~13 min |
For a group of multiple batteries, divide the total load by the number of batteries and refer to this table. For example, in a group of 20 batteries, a load of 12,000 W is 600 W per battery.
How was it calculated? The constant power table in the datasheet (25 °C, 1.75 V cut-off per cell) was used; the inverter efficiency of the UPS when operating from the battery was considered to be 85%. In a group connected in series, each battery gives an equal share of the total power. Detail of the method: How to calculate battery time?
Manufacturer's discharge values (single battery, 25 °C, 1.75 V cut-off per cell — most UPSs disconnect at this voltage):
| Duration | Constant current | The power of the battery |
|---|---|---|
| 5 min | 241.8 A | 2,619 W |
| 10 min | 171.3 A | 1,876 W |
| 15 min | 154.2 A | 1,705 W |
| 30 min | 98.2 A | 1,108 W |
| 1 hour | 59.5 A | 684 W |
| 2 hours | 36.3 A | 419 W |
| 5 hours | 17.8 A | 209 W |
| 20 hours | 5.2 A | 62 W |
The actual time varies according to the age of the battery, the ambient temperature and the variability of the load; it is significantly shortened in aged batteries.
Choosing the right battery
- Voltage: 12 V. The voltage on the label of the battery in your device must be the same.
- Size: 330 × 173 mm base, 220 mm height with poles (± 3 mm). Fit in the battery compartment or cabinet shelf, with space at the top for cables and terminal covers.
- Pole Type: With M8 bolt (T11). The lugs of the connection cables must match the M8 bolt.
- Capacity: All batteries in a group must be of the same capacity. The longer the capacity, the longer the time; the charging current of the UPS or charger must be sufficient, otherwise the full charge time will be longer. Equally higher capacity model: BC105-12.
- Type: UPSs charge according to the dry type (VRLA-AGM) battery; the flooded (well-maintained) automobile battery is not installed in the UPS.
- Batteries in the array: It must be the same model and, if possible, from the same production date.
Charging, mounting and safety
- Standby (buffer) charging: 13.60 – 13.80 V at 25 °C, temperature correction –18 mV/°C. UPSs and alarm panels make this setting themselves.
- Cyclic charging: 14.50 – 14.90 V at 25 °C, temperature correction –30 mV/°C. If you are charging with a separate charger, use an AGM set device that matches these values.
- Assembly: Turn off the UPS and turn on the battery fuse or switch; do not reverse the polarity (red +, black –). Tighten the bolts to the manufacturer's recommended torque, install the terminal caps — the loose connection will heat up.
- Short Circuit: the short-circuit current of the battery is 2,000 A. Do not touch the two poles at the same time with the metal tool, remove the ring and watch when installing; use insulated tooling.
- Transportation: The battery weighs approx. 27.8 kg; do not lift it by the poles, but carry it with two people or appropriate equipment.
- Environment: Use the batteries in a ventilated location away from the heat source and direct sun.
Life, storage and change
- Design life: 10 years in buffer use at 20 °C. Real life; It depends on the ambient temperature, number and depth of discharge. Keeping the environment where the batteries are located at 20-25 °C preserves life.
- Temperature: the capacity is 103% at 40 °C, 100% at 25 °C, and 86% at 0 °C; although the capacity increases slightly in the heat, the life is shortened.
- Storage: while the battery is unused, it discharges at most 3% per month at 25 °C; it should be kept for a maximum of 6 months and then refresh charged, more frequently in hot environment.
- Time to change: If the duration of the UPS has shortened significantly, if it gives a battery warning or if the battery is swollen, it is time for a replacement. When should a UPS battery be replaced?
- Waste battery: Used batteries are not disposed of in household waste; they are handed over to waste battery collection points.
Battery replacement and Periodic Maintenance With our services, we measure your batteries and replace them on time.
| Nominal voltage | 12 V |
|---|---|
| Nominal capacity | 100 Oh |
| Battery technology | VRLA – AGM (maintenance-free, dry type) |
| Design life | 10 year |
| Pole (terminal) type | M8 bolt-on |
| Dimensions (L × W × H) | 330 × 173 × 213 mm |
| Total height (with pole) | 220 mm |
| Internal resistance | approximately 4.9 mΩ |
| Short circuit current | 2000 A |
| Case material | ABS |
| Time for which rated capacity is measured | 10 hours of discharge (C10) |
| Polar code (manufacturer) | T11 |
| Standby (buffer) charging voltage, 25 °C | 13.60 – 13.80 V (temperature correction –18 mV/°C) |
| Cyclic charging voltage, 25 °C | 14.50 – 14.90 V (temperature correction –30 mV/°C) |
| Operating temperature | Discharge –15 ... 50 °C · Charge –20 ° 40 °C · Storage –15 ... 40 °C |
| Recommended operating temperature | 25 ± 3 °C |
| Effect of temperature on capacity | 40 °C 103% · 25 °C 100% · 0 °C 86% |
| Self-emptying | Up to 3% per month at 25 °C |
| Storage | Maximum 6 months at 25 °C, then refresh charge (more frequent in heat) |
| Dimension tolerance | ± 3 mm |
| Warranty | 2 year |
| Weight | 27,8 kg |
| Status | Zero |
| Stock | Sold out |
Batteries are delivered with their original pole protectors and without any connection to the poles. For withdrawal, the battery must not be used, charged/discharged and the terminals must not be connected; batteries that are installed and used will not be returned or will be deducted from the loss of value. Check the capacity and size suitable for your UPS before ordering; in case of wrong selection, the return shipping is your responsibility.
Delivery Process
- It will be shipped within 1–3 business days.
- The tracking number is shared by email and in My Account → My Orders.
- When picking, check the package with the cargo officer; if there is damage, make a report and do not receive it.
- Heavy and multi-volume shipments are delivered by warehouse or vehicle; the time and fee are shown according to your address in the payment step.
Returns and exchanges
- You can exercise your right of withdrawal within 14 days of delivery (individual purchases).
- The product to be returned must be unused, in its original packaging, complete with the invoice and accessories.
- Loss of value is deducted from products that have been installed and used, terminals connected or commissioned; if the use has made it impossible to return, the return will not be accepted.
- Return shipping cost belongs to the buyer; For defective, damaged or incorrectly sent products, the price belongs to us.
- Refunds will be made to your payment method no later than 14 days after the product has been received and inspected.
- The legal right of withdrawal does not apply to corporate (commercial purposes) purchases; requests are evaluated separately.
Customer reviews
There are no reviews for this product yet.
If you've used this product, share your experience—be the first to leave a review.
Rate this product
- Your rating and a few sentences will help guide other customers.
- You decide whether your name, city, and photo will be displayed.
- If you purchased it from us, the "Purchased" badge will appear in your review.
Log in to post a comment.