Should a Single Battery or the Whole Group Be Replaced in a UPS?

Should a Single Battery or the Whole Group Be Replaced in a UPS?

One battery is marked in red on the maintenance report, the others look good. The first question that comes to mind is: isn't it enough to just replace that battery? Sometimes enough; sometimes the new battery wears out in a short time among the old ones and the expenditure is wasted.

How to understand the time for change When to replace a UPS battery We explained it in our article. In this article, we focus on only one question: should the faulty battery be replaced alone or with the whole group?

In a series array, the batteries are not independent of each other

UPS battery groups are mostly made up of batteries connected in series, and the same current flows through all the batteries in the array. Therefore, the array as much as the weakest battery withstands. In an outage, the battery with low capacity is discharged before the others; Since the UPS mostly looks at the total voltage, this battery can discharge very deeply and wear out even more, while the total is still sufficient.

The basis of series and parallel connection Battery Array and Series-Parallel Connection We explained it in our article.

New Battery in Old Array: What Happens?

When a single new battery is installed in an aged array, the following problems occur together:

  • Voltage sharing is disrupted in charging: The UPS applies a single total voltage to the array. This voltage is shared among the batteries according to their internal condition; batteries with different ages and wear levels do not receive an equal share. Some of them are overcharged and heated, some of them are never fully charged.
  • The period does not come back: Even if the capacity of the new battery is full, the old batteries determine the duration of the array. Expenditure is made, but the period of interruption does not extend as much as expected.
  • The new battery also wears out: Unbalanced charging and deep discharges also age the new battery at the rate of the old ones.

Therefore, it is generally not recommended to renew a single battery in an aged array.

When Might a Partial Exchange Be Appropriate?

Partial change is not wrong in all cases. It can be considered if the following conditions are met together:

  • Series is new and the single battery failed prematurely; the age of the others is at the beginning of its design life.
  • Voltage and internal resistance values are close to each other, not significantly diverged from the initial values.
  • The new battery is of the same type, same capacity and suitable specification; the date of manufacture is as close as possible to those in the series.
  • The battery manufacturer's instruction allows partial replacement; the state of charge and voltage are checked before installation.

Premature failure of a single battery in a new string may indicate a manufacturing defect; if this happens, the replacement may be covered by the warranty. The scope and terms of the warranty vary depending on the battery manufacturer.

When is the whole group renewed?

  • Batteries are nearing the end of their design life.
  • The internal resistance of more than one battery is markedly separated from the initial value or string average.
  • Capacity testing showed that the group failed to deliver the expected backup time.
  • More than one battery is swollen, leaking, or overheating.
  • The group experienced an event that affected all batteries, such as overheating or very deep discharge.

What the measurement tells What is battery internal resistance?, capacity test How to perform a battery discharge test You can find it in our article.

Series-Based Decision in Parallel Arrays

In systems with more than one parallel array, the decision is made series by array. The batteries of each array are measured separately. If there is a problem with a single array in a young system, only the condition of the batteries in that array is evaluated; if all the arrays are old, the whole group is considered to be renewed together.

New and old batteries are not mixed in the same string. Adding a new string in parallel to an aged group to increase capacity is also carefully considered: the strings may not share the load equally; the string to be added must be of the same type and specification, and the decision must be made according to the manufacturer's instructions. Measurements are repeated after each change, as the current distribution between the strings may vary.

Decision Criteria Together

StatusUsually evaluated
New series, single battery fails early, others are consistentSingle battery replacement; warranty coverage is examined separately
Middle-aged knee, a battery dissociatedDecision by measurement and, if necessary, capacity test
A series near the end of its lifeRenewal of the entire series
Multiple batteries are degraded or damagedRenewal of the entire series
Only one of the parallel sequences is problematicDecision on the basis of the series according to the situation of that series

The table is a frame. The decision to replace a partial or complete battery pack is made in accordance with the condition of the existing batteries and the manufacturer's instructions.

Decision is Made by Measurement

The external view of the battery or a single warning on the UPS screen is not enough to make a decision. The voltage and internal resistance per battery are measured, the values are compared with each other and with previous measurements; capacity testing is performed when necessary. How to choose a new battery How to choose a UPS battery, the process of change How to replace a UPS battery We explained it in our articles.

Battery banks carry dangerous DC voltage even when the UPS is turned off. Measurement, string separation and battery replacement Authorized Technical Personnel with insulated tools and in accordance with the manufacturer's instructions.

Decision Criteria at a Glance

Whether the faulty battery will be replaced alone or with the group is determined by looking at six criteria together.

No criterion alone is enough; the decision is made by the measurement results and the manufacturer's instructions. You can find the details in the rest of the article.

Frequently Asked Questions

01Can a single battery be replaced in a UPS?
It can be replaced; but only if the string is new, the measurements of the other batteries are consistent, and the manufacturer's instruction allows. It is generally not recommended to rebuild a single battery in an aged string.
02What is the drawback of installing new batteries next to old ones?
In a series array, batteries share the charging voltage according to their internal state. Batteries with different ages and internal resistance do not charge equally; the duration of the series is determined by the old batteries and the new battery wears out in a short time.
03A battery failed in the new array, is it under warranty?
Premature failure may indicate a manufacturing defect and may be considered under warranty. Coverage and conditions are determined by the battery manufacturer's warranty.
04Do all batteries change in a parallel array system?
Not always. The decision is made by measuring series by series. If the series are young and only one is problematic, that series is evaluated; if all of them are old, the whole group is considered to be renewed.
05Who makes the decision?
Voltage and internal resistance measurements per battery are given by authorized technical personnel, if necessary, by evaluating the capacity test and manufacturer instructions together.

Let's Evaluate Your Batteries Together

We measure and replace UPS batteries of all brands and models throughout Istanbul and in the surrounding provinces. How the decision to partially replace or renew the group is made Battery Replacement and Reconditioning page. Your last maintenance report, the make and model of your UPS and the information on the battery labels Send us; Let's evaluate it together.