How to Choose a UPS Battery? 7 Criteria for the Right Battery

How to Choose a UPS Battery? 7 Criteria for the Right Battery

The most common mistake made when replacing a battery is choosing a new one simply because it fits in the compartment, based on the voltage and Ah rating listed on the old battery’s label. However, two batteries of the same size and Ah rating can behave very differently under the high current drawn by the UPS during a power outage.

The steps in the change process How to Replace a UPS Battery We explained this in our previous article. In this article, we focus solely on the selection process and explain the criteria used to determine the right battery.

1. System Voltage and Configuration

The UPS inverter operates at a specific DC bus voltage; the battery voltage and the number of batteries in the string must be compatible with this voltage. The number of batteries in a string and the number of parallel strings vary depending on the UPS model and are specified in the manufacturer’s documentation. In some UPS units that use an external battery bank, the number of batteries must also be entered into the device’s settings; if this setting is incorrect, the batteries may be charged at the wrong voltage. Details battery bank and series-parallel connection in our article.

2. Capacity and Backup Time: Oh, That’s Not Enough

The Ah rating on a battery label is typically specified for a slow discharge lasting 20 or 10 hours. A UPS, on the other hand, usually discharges the battery at a high current for a period ranging from a few minutes to half an hour. For this reason, the catalogs for UPS batteries specify the power that can be delivered per cell for a given duration and end-of-discharge voltage. W/Cell Tables ...is found. A 12-volt lead-acid battery consists of six cells.

The logic behind the calculation What is the battery capacity in Ah? Let’s continue with the example from our article (a 6,000 W load, a single string consisting of 20 batteries):

My NameWhat should be done?Example
Power to be drawn from the batteriesThe load power is divided by the inverter's efficiency.6,000 W ÷ 0.9 ≈ 6,670 W
Power per cellThis power is divided by the total number of cells in all arrays.20 × 6 = 120 cells; 6,670 ÷ 120 ≈ 55.6 W/cell
Depreciation allowanceA battery is considered to have reached the end of its service life when its capacity drops to roughly 80% of its rated value. To ensure the required runtime at that point, a factor of 1 ÷ 0.8 = 1.25 is commonly added; an additional temperature factor may also be required for cool environments.55.6 × 1.25 ≈ 69.5 W/cell
Selecting from a tableSelect a battery that provides at least this value for the desired runtime and the UPS’s end-of-discharge (EOD) voltage.For example, at least 69.5 W per cell in 10 minutes

The values are for illustrative purposes only; actual calculations are based on the UPS and battery documentation and the current load, as loads may have changed since installation. Batteries designed to deliver high power for short periods high current (high rate) They are known as batteries; they can deliver more power in short bursts than a general-purpose battery with the same Ah rating. The approximate requirement Power Calculation You can see it with our vehicle.

3. Technology and Design Lifespan

VRLA (AGM or gel) batteries are most commonly used in UPS systems. Different battery technologies cannot be used interchangeably simply because they have the same dimensions; their charging voltages and discharge behaviors differ. The differences VRLA, AGM, and gel batteries In our article, the conditions for the transition to lithium lithium-ion UPS batteries We explained this in our article.

The battery's design life class is also part of the selection process. Which lifespan class is selected depends on the importance of the system and how much longer the UPS will be used. The classes When should a UPS battery be replaced? We summarized this in our article.

4. Dimensions and Connection Structure

  • Dimensions and weight: The battery must fit in the cabinet or on the shelf, and the load capacity of the shelf and floor must not be exceeded.
  • Terminal type: Small batteries have push-in terminals, while large ones have screw terminals; the connectors must be compatible with this type.
  • Terminal layout: If the positions of the positive and negative terminals differ from those on older batteries, the cables may not be long enough, or the connection configuration may change.
  • Cables and protection: The cable cross-section, fuses, and terminal covers are checked against the new batteries.

5. The UPS Charging System

When the mains power is available, the UPS keeps the batteries charged at a constant float voltage. The charging voltage recommended by the manufacturer for a new battery must be compatible with the UPS settings. If the capacity is to be increased, it must also be determined whether the UPS’s charging power can fully charge this capacity within a reasonable time. Some UPS manufacturers specify additional requirements for battery type and capacity; the selection must be made in accordance with these requirements. Post-replacement configuration checks Commissioning after a battery replacement We explained this in our article.

6. Production Date and Shelf Life

Lead-acid batteries gradually discharge even when not in use; a battery left uncharged on a shelf for a long time may lose capacity. For this reason, the production dates of the batteries are checked. Batteries in a set should be of the same type and capacity, and their production dates should be close to one another. Batteries stored in the warehouse are tested before installation, and if necessary, a refresh charge is performed as recommended by the manufacturer. Details Factors Affecting Battery Life in our article.

7. Brand and Warranty

The new battery does not have to be the same brand as the old one; it must be electrically and technically compatible. Batteries are covered by the manufacturer’s warranty; the duration and terms of the warranty are clarified during the battery selection and quotation process.

If only some of the batteries in the series are to be replaced, the options are even more limited; this situation Should just one battery be replaced, or the entire set? We covered this in our article. For small plug-in UPS units, the battery type specified in the user manual should be used. Battery replacement and, especially in systems connected to a control panel, selection and installation qualified technical staff must be done by.

  1. EUROBAT — Guide to VRLA Stationary Batteries (2022) (calendar life classes; the effect of temperature on service life)
  2. IEC 60896-21/-22 — Stationary lead-acid batteries, valve-regulated types: test methods and requirements
  3. Product manuals and data sheets from UPS and battery manufacturers (specifications vary by manufacturer)

Sources

Battery selection at a glance

The right UPS battery is not selected by looking at a single value, but by performing all of these checks together.

When one of the checks is skipped, the problem often occurs at the first interruption. You can find the details of each criterion later in the article.

Frequently Asked Questions

01Will every battery with the same volt and Ah rating fit a UPS?
It may not fit. The Ah value is given for slow discharge; UPS, on the other hand, discharges the battery with high current in a short time. The selection is made with the battery manufacturer's W/cell tables, with the size, terminal and charging match.
02Will the time be extended if a battery with a higher Ah value is installed?
It usually gets longer; however, the dimensions of the battery, the terminal structure and the charging power of the UPS should also be appropriate. Large capacity batteries take a long time to fill up and some UPSs also need to change the capacity setting.
03Do new batteries need to be the same brand as the old ones?
Not required. It must be suitable for the UPS and battery layout in terms of voltage, capacity, technology, size and connection structure.
04Can an AGM battery be installed instead of a gel battery?
Different technologies are not used interchangeably because they only keep measurements. If the technology is to change, the charging settings of the UPS must be appropriate for the new battery and different technologies must not be mixed in the same sequence.
05How long is the warranty on the batteries?
The batteries used in battery replacement are guaranteed by the manufacturer. The duration and conditions are clarified at the battery selection and proposal stage.

Let's Choose the Right Battery Together

We select and replace batteries for UPS of every brand and model throughout Istanbul and in the surrounding provinces. What is looked at in the selection Battery Replacement and Reconditioning page. The make and model of your UPS, the number of batteries, the information on the battery labels and the desired backup time Send us; Let's determine the appropriate battery together.

Bempower https://www.bemenerji.com/en/blog/how-to-choose-a-ups-battery-7-criteria-for-the-right-battery
Write via WhatsApp